2.6 Configuring the System Mode

Alarm/Relay/Remote

2. Click here (also selectable from [Setting] - [System Mode Setting]).

1. Select this tab.

Remote control

terminal number

Resets the range

selection.
Copy and paste the

selected range

(see page 4-15).

Select actions.

Alarm/Relay

• Reflash

When multiple alarms are set to one alarm output relay, this function notifies the

succeeding alarms after the first alarm that causes the relay activation.

• Relay AND

Set the range of relays (from the first alarm relay) to take the AND logic. All other

relays will be set to OR logic. If [NONE] is selected, all relays will operate using the
OR logic.
• AND: Activated when all alarms are being generated simultaneously.
• OR: Activated when at least one of the alarms is being generated.

• Relay Action

Select whether to energize or de-energize the alarm output relay when the alarm

occurs.

• Alarm Relay Behavior

• Unhold: Turns OFF the output relay when the cause of the alarm is no longer met.
• Hold: Holds the output relay ON until the alarm acknowledge operation is executed.

• Alarm Indicator

Unhold, Hold: See “Alarm Relay Behavior.”

When [Alarm Relay Behavior] is set to [Hold], only [Hold] can be selected for the [Alarm

Indicator].

• Rate of Change Increase/Rate of Change Decrease

Select the time interval for the rate of change alarms in terms of the number of

samplings (1 to 15).

Interval = scan interval × number of samplings

• Alarm Hysteresis

A width (hysteresis) of 0.5% of the display span can be specified on the value used

to set or release the alarm. This applies to upper (H) and lower (L) limit alarms on
measurement channels.