5 configuring the engineering mode, Screen display, 5 configuring the engineering mode -14 – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 26: Screen display -14
2-14
IM04L41B01-65EN
2.5 Configuring the Engineering Mode
Screen Display
Select this tab.
Recovers by a key operation.
Recovers by a key operation or alarm occurrence.
The backlight saver function is
activated, when there is no key
operation or alarm occurrence
for the “Saver time.”
Select the time per division
Line width
1 to 3 dots
On: Use
Off: Not use
Select the display
direction of the trend
and bar graphs.
Set the screen
background color to
white or black.
Display Update Interval
You can select the display update interval from [1 min/div], [2 min/div], [5 min/div], [10
min/div], [15 min/div*], [20 min/div], [30 min/div], [1 h/div], [2 h/div], [4 h/div], and [10
h/div]. In addition to these selections, [15 sec/div] and [30 sec/div] can also be selected
on the DX102P, DX104P, DX204P and DX208P.
* A [15 min/div] is for the DXP style S4 or later only.
Auto Save Interval
You can set the interval, if the data type is set to [DISPLAY] in the memory sample
settings of the system mode tab. However, if the type of process is set to [Batch]
in the application settings of the system mode tab, the maximum selectable time is
automatically entered and cannot be selected.
Grid Division
Select number of grids on the waveform display area from [Auto] or [4] to [12].
Auto: Display the same number of grids as the number of scale divisions of the first
assigned channel of the group.
Auto Scroll Time
This is the time period used to automatically switch the displayed group. Select the time
period from [5 s], [10 s], [20 s], [30 s], or [1 min].
LCD Brightness
Select the brightness of the screen from [1] to [8] (DX100P), or [1] to [4] (DX200P). A
higher value corresponds to a brighter screen setting.