beautypg.com

Profibus dp rui/gtw led indicators – Watlow EZ-ZONE RUI/Gateway User Manual

Page 41

background image

Watlow EZ-ZONE

®

RUI/Gateway

38

Chapter 5 Networking with a Gateway

Slot Offset = 61

Index = 0

Profibus DP RUI/GTW LED Indicators

Viewing the unit from the front and then looking on

top of the RUI/GTW two bi-color LEDs can be seen

where only the front one is used. Definition follows:

Closest to the Front

Indicator LED

Description

Red

Profibus network not detected

Red

Flashing

Indicates that the Profibus card is

waiting for data exchange.

Green

Data exchange mode

To learn more about Profibus DP point your browser

to:

http://www.profibus.org

As with all of the other available protocols prior

to establishing communications between Master and

the slave the gateway instance must first be enabled

[du;en]

. Once enabled, the user must define the Slot

Offsets for each enabled EZ-ZONE controller.

Use the graphic below (RUI being used as a Profi-

bus DP Gateway) in reference to the descriptions that

follow below.
[`s;of]

Slot Offsets are used exclusively with acyclic

(DP-V1) communications and define the in-

dividual EZ-ZONE controller on the network

as well as the instance of the parameter to

be read or written to. The offset defaults are

as shown in the graphic in increments of 20,

however, they can be changed based on user

needs.

As an example, when programming the Master device

ensure that the Slot Offset and the Profibus Index

(found in each product user manual in the various

menus) are defined. To read the first instance of the

Process Value in PM2 use the following information

when programming the Master:

Slot Offset = 20

Index = 0 (See the EZ-ZONE PM Users Manual,

Operations Page under the Analog Input

Menu)

Note that PM2 and instance 1 is identified in the

Slot Offset where the parameter, in this case, Process

Value 1 is identified via the Profibus Index. If it were

instance 2 same parameter that was needed the Slot

Offset would change to 21.
Likewise, to read the Process Value instance 2 of PM4

the following information would need to be entered

when programming the Master:

[gtW]

1 = PM1

[gtW]

4 = PM4

Address Lock

[a;loc]

= [yes] or [no]

[Com]

Instance 2

Units

[`C_f]

= [``f] or

[``C]

Profibus DP

Watlow Standard Bus

(Daisy chain EIA-485)

EZ-ZONE

®

Controllers

1 - 16 maximum

Profibus Slot

Offset

0

Profibus Address

[p;add]

= 0 - 126

[Com]

Instance 1

Standard Bus Address

[Ad;S]

= 1-8

Start Node to Scan

[St;2n]

= 1-24

End Zone to Scan

[nU;2n]

= 1-24

RUI/Gateway

Setup Prompts

Profibus DP

[gtW]

= 1 – 16

(Gateway Instance)

[Du;En]

= Yes or No

(Enable gateway instance)

Gateway

[Du;st]

= [On] or [off]

(Device Status)

[`s;of]

= 0 - 254

(Profibus Slot Offset)

Profibus Slot

Offset

20

Profibus Slot

Offset

40

Profibus Slot

Offset

60