Watlow EZ-ZONE RUI/Gateway User Manual
Page 21
Watlow EZ-ZONE
®
RUI/Gateway
•
18
•
Chapter 3 Keys and Displays
EZ-ZONE PM Home Page
Custom
Menu
Number
Home
Page
Display
Home Page Defaults
Custom
Menu Dis-
play
(defaults)
Parameter Page and Menu
All Models
1
Numerical
value
Active Process Value (1)
[AC;Pu]
Operations Page, Monitor Menu
2
Numerical
value
Active Set Point (1)*
[AC;SP]
Operations Page, Monitor Menu
IF 10
th
digit of PN is equal to: PM _ _ _ _ _ - _ [L, M] _ _ _ _ _
3
Numerical
value
Process Value (2)
[AC;Pu]
Operations Page, Monitor Menu
4
[safe]
or
[fail]
Limit Status
[AC;SP]
Home Page
IF 10
th
digit of PN is equal to: PM _ _ _ _ _ - _ [A, C, J, R, P, T] _ _ _ _ _
3
[pu;a2]
Active Process Value (2)
[AC;Pu]
Operations Page, Monitor Menu
4
[C;sp2]
Closed Loop Set Point
(2)
[AC;SP]
Operations Page, Monitor Menu
5
[C;M1]
User Control Mode (1)
[`C;m]
Operations Page, Monitor Menu
6
[h;pr1]
Heat Power (1)
[`h;Pr]
Operations Page, Monitor Menu
7
[C;pr1]
Cool Power (1)
[`C;Pr]
Operations Page, Monitor Menu
8
[aut1]
Autotune (1)
[`AUt]
Operations Page, Loop Menu
9
[id;s1]
Idle (1)
[idLE]
Operations Page, Loop Menu
10
[C;m2]
User Control Mode (2)
[`C;m]
Operations Page, Monitor Menu
11
[h;pr2]
Heat Power (2)
[`h;Pr]
Operations Page, Monitor Menu
12
[C;pr2]
Cool Power (2)
[`C;Pr]
Operations Page, Monitor Menu
13
[aut2]
Autotune (2)
[`AUt]
Operations Page, Loop Menu
14
[id;s2]
Idle (2)
[idLE]
Operations Page, Loop Menu
IF 10
th
digit of PN is equal to: PM _ _ _ _ _ - _ [L, M] _ _ _ _ _
15
[ll;s1]
Limit Set Point Low
[`ll;s]
Operations Page, Limit Menu
16
[lh;s1]
Limit Set Point High
[`lh;s]
Operations Page, Limit Menu
IF 10
th
digit of PN is equal to: PM _ _ _ _ _ - _ [R, B, N, E] _ _ _ _ _
17
[p;st1]
Start Profile
[P;Str]
Home Page only (See Profile Page Chapter.)
18
[p;aC1]
Action Request
[P;ACr]
Home Page only (See Profile Page Chapter.)
19
None
20
None
*
If Control Mode is set to Auto, the process value is in the upper display and the Closed Loop Set Point
(read-write) is in the lower display.
If a profile is running, the process value is in the upper display and the Target Set Point (read only) is in
the lower display.
If Control Mode is set to Manual, the process value is in the upper display and the output power level (read-
write) is in the lower display.
If Control Mode is set to Off, the process value is in the upper display and [`oFF] (read only) is in the lower
display.
If a sensor failure has occurred, [----] is in the upper display and the output power level (read-write) is in
the lower display.
Note:
Numbers within parenthesis indicates the instance.