beautypg.com

Using modbus tcp, Ethernet rui/gtw led indicators – Watlow EZ-ZONE RUI/Gateway User Manual

Page 39

background image

Watlow EZ-ZONE

®

RUI/Gateway

36

Chapter 5 Networking with a Gateway

outputs from the Master and is used exclu-

sively when communicating implicitly. For

any given RUI gateway instance (EZ-ZONE

controller), the input assembly size will never

be greater than 20, 32-bit members. The user

entry ranges from 0 to 20.

Note:

The maximum number of implicit input/output

members using EtherNet/IP cannot exceed 100. A

network could have up to 5 EZ-ZONE controllers

with 20 members each maximum or the 100 mem-

bers can be divided any way the user would like

as long as 20 I/O members per controller are not

exceeded.

Using the graphic on the following page as an ex-

ample, if:

[Gtw]

instance 1 has [ai;nb] and [ao;nb] set to 5

[Gtw]

instance 2 has [ai;nb] and [ao;nb] set to 5

[Gtw]

instance 3 has [ai;nb] and [ao;nb] set to 5

[Gtw]

instance 4 has [ai;nb] and [ao;nb] set to 5

Each of the four EZ-ZONE family controllers will

contain the first 5 members of the assembly and this

information would then be passed implicitly to the

Master on the EtherNet/IP network.

Using Modbus TCP
Communications To/From a Master:

When Modbus TCP is enabled there are Modbus re-

lated prompts (violet as shown in graphic) that need

to be addressed. They are:

1. Modbus TCP Enable [mb;e], turns Modbus on or

off.

2. Modbus TCP Word Order [m;hl], which allows

the user to swap the high and low order 16 bit

values of a 32-bit member.

3. Modbus TCP Offset [m;of], which defines each of

the available Modbus registers for each gateway

instance.

As an example, when using Modbus TCP notice that

the Modbus offset now applies. For the purpose of

this discussion assume the offsets are as shown in

the graphic on the following page and the Master

wants to read the first instance of Closed Loop Set

Point from both Standard Bus address 1 and 4. Open

up the appropriate PM users manual and go to the

Operations Page, Loop Menu to find the Closed Loop

Set Point.
Note:

If using a legacy EZ-ZONE ST controller with a

firmware version less the 3.0, consider using the

Modbus addresses listed in the ST user manual

in the column entitled "RUI/GTW Modbus". If the

firmware in the ST is 3.0 or higher new features

were added and made accessible through the Map2

registers. If interested in using the new features

today or perhaps in the future configure the ST for

Map 2 Modbus registers.

When found, notice that the relative Modbus regis-

ter is 2160 (Map 1) or 2640 (Map 2). To read the set

point from address 1 the appropriate absolute Mod-

bus address would be:

2160 + 400001 + Modbus offset (0) = 402161.

To read the Closed Loop Set Point from Standard Bus

address 4 the absolute address would be:

2160 + 400001 + Modbus offset (15000) = 417161.

Note:

To minimize traffic and enable better throughput

on Standard Bus, set the End Zone prompt [nU;2n]

in the RUI to the maximum number of EZ-ZONE

controllers on the network to be scanned.

Note:

The RUI/GTW allows for a maximum entry of 9999

due to limitations of the 7 segment display. To en-

ter a Modbus offset > 9999 EZ-ZONE Configurator

must be used..

Note:

In the above graphic there are several prompts

omitted for the sake of saving some space. When

the Ethernet addressing mode is set to Fixed the

user will find several more prompts that will follow

the prompt shown for "Ethernet Addressing Mode"

related to specifying the actual IP [ip;f1] - [ip;f4],

subnet [ip;s1] - [ip;s4] and the gateway [ip;g1]

- [ip;g4] (external gateway) addresses. If set to

receive an IP address from a host [dhCp]computer,

the prompts shown above are accurate.

Note:

When changing the RUI/GTW IP address, power

must be cycled for the new address to take effect.

Ethernet RUI/GTW LED Indicators

Viewing the unit from the front and then looking on

top of the RUI/GTW four LEDs can be seen aligned

vertically front to back. The LEDs are identified ac-

cordingly: closest to the front reflects the Network

(Net) status, Module (Mod) status is next, Activity

status follows and lastly, the LED closest to the rear

of the RUI/GTW reflects the Link status.