beautypg.com

Using devicenet – Watlow EZ-ZONE RUI/Gateway User Manual

Page 36

background image

Watlow EZ-ZONE

®

RUI/Gateway

33

Chapter 5 Networking with a Gateway

using CIP can be accomplished via explicit and or im-

plicit communications. Explicit communications usu-

ally requires the use of a message instruction within

the Programmable Logic Controller (PLC) but there

are other ways to do this as well. Implicit communica-

tions is also commonly referred to as polled communi-

cations. When using implicit communications there is

an I/O assembly that would be read or written to; the

default assemblies are embedded into the firmware

of the controller and are different for each. Watlow

refers to these assemblies as the T to O (Target to

Originator) and the O to T (Originator to Target) as-

semblies where the Target is always the EZ-ZONE

controller and the Originator is the PLC or Master

on the network. The O to T assembly is made up of

20 (32 bit) members that are user configurable where

the T to O assembly consists of 21 (32 bit) members.

The first member of the T to O assembly is called the

Device Status, it is unique to the RUI/GTW and can-

not be changed. Bits 16 - 31 of this 32 bit word rep-

resents the communications status of the EZ-ZONE

controllers on the Standard Bus side of the RUI/GTW

when enabled. Once a Zone is enabled, valid commu-

nications will be represented with the bit set to a "1",

if set to "0", the RUI/GTW is not communicating with

the zone. Bit 16 represents Zone 1 where bit 31 rep-

resents Zone 16. The 20 members that follow Device

Status are user configurable. The Appendix of this

user manual contains the assemblies for each of the

EZ-ZONE controllers. (

See

Appendix:

CIP Implicit As-

semblies

by product).

To change any given member of either assembly

simply write the new class, instance and attribute to

the member location of choice. As an example, if it

were desired to change the 14

th

member of the O to

T assembly of an EZ-ZONE PM Integrated controller

(PM1) from the default parameter (Heat Proportional

Band) to Limit Clear Request (see Operations Page,

Limit Menu) write the value of 0x70, 0x01 and 0x01

(Class, Instance and Attribute respectively

)

to 0x77,

0x01 and 0x0E. Once executed, writing a value of zero

to this member will reset a limit assuming the condi-

tion that caused it is no longer present.
Note:

When changing the implicit assembly of any given

controller through the RUI/GTW ensure that the

CIP Instance Offset is added to the documented

instance for any given parameter as well as the as-

sembly instance. As an example, if it were desired

to do the above operation on PM3 the value to write

would now be 0x70, 0x

09

and 0x01 (Class, Instance

and Attribute respectively

)

to 0x77, 0x

09

and 0x0E.

Notice that the CIP Offset was added to each.

Using DeviceNet™
Communications To/From Third Party Device:

When using the DeviceNet protocol, there are two

methods used in communicating, implicitly and ex-

plicitly. Once the gateway instance is enabled there

are two prompts that relate directly to these forms of

communication.

Use the graphic below in reference to the descrip-

tions that follow.

[`ost]

CIP Offset, used exclusively with explicit

messaging where it defines a specific gateway

instance (EZ_ZONE PM or RM controller) to

receive a message originating from the net-

work Master. The CIP offset is unique to each

gateway instance and is added to the pub-

lished instance of any given parameter.

As an example, when programming the explicit mes-

sage ensure that the class, instance and attribute are

defined. To read the first instance of the Process Vari-

able in PM2 (see graphic on next page) use the follow-

TM

RUI/Gateway

Setup Prompts

[gtW]

1 = PM1

[gtW]

4 = PM4

TM

Gateway

Watlow Standard Bus

(Daisy chain EIA-485)

EZ-ZONE

®

Controllers

1 - 16 maximum

CIP Offset

13-16

CIP Offset

9-12

CIP Offset

5-8

CIP Offset

1-4

[oSt]

= 0 - 255

(CIP Offset)

DeviceNet

TM

[Ao;nb]

= 0 - 20

CIP Output Assembly Size

[Ai;nb]

= 0 - 20

CIP Input Assembly Size

[gtW]

= 1 – 16

(Gateway Instance)

[Du;En]

= Yes or No

(Enable gateway instance)

[Du;st]

= [On] or [off]

(Device Status)

[Com]

Instance 1

Standard Bus Address

[Ad;S]

= 1-8

Start Node to Scan

[St;2n]

= 1-24

End Zone to Scan

[nU;2n]

= 1-24

DeviceNet

TM

Node Address

[ad;d]

= [0-63]

[Com]

Instance 2

Network Baud Rate

[baud]

= [125], [250], or

[500]

Kb

DeviceNet

TM

Quick Connect

[FC;e]

= [yes] or [no]

Units

[`C_f]

= [``f] or [``C]