beautypg.com

Devicenet rui/gtw led indicators – Watlow EZ-ZONE RUI/Gateway User Manual

Page 37

background image

Watlow EZ-ZONE

®

RUI/Gateway

34

Chapter 5 Networking with a Gateway

ing information in the message instruction:

Class = 104 or (0x68)

Instance = 1

Attribute = 1

Note that the instance is identified as instance 1 be-

cause there is no offset to add. RUI prompt entry for

gateway instance 1 follows:
[`oSt]

= 0

RUI prompt entry for gateway instance 2 (PM2) fol-

lows:
[`oSt]

= 4

RUI prompt entry for gateway instance 3 follows:
`oSt]

= 8

RUI prompt entry for gateway instance 4 follows:
[`oSt]

= 12

To read the process value instance 2 of PM4 add

the offset to the instance. The following information

would need to be entered in the message instruction:

Class = 104 or (0x68)

Instance = 14 or (0x0E)

Attribute = 1

[ao;nb]

From the gateway perspective, this assembly

represents data that comes from Standard

Bus controllers (EZ-ZONE PM or RM) and

is sent out on the network. As seen from the

network, this is the CIP Implicit Output As-

sembly representing inputs to the Master

and is used exclusively when communicat-

ing implicitly. For any given RUI gateway

instance (EZ-ZONE controller), the output

assembly size will never be greater than 20,

32-bit members. The user entry ranges from

0 to 20.

[ai;nb]

From the gateway perspective, this assembly

represents data that comes from the network

Master and is sent to one or more gateway

instance (EZ-ZONE PM or RM) on Standard

Bus. As seen from the network, this is the

CIP Implicit Input Assembly representing

outputs from the Master and is used exclu-

sively when communicating implicitly. For

any given RUI gateway instance (EZ-ZONE

controller), the input assembly size will never

be greater than 20, 32-bit members. The user

entry ranges from 0 to 20.

Note:

The maximum number of implicit input/output

members using DeviceNet cannot exceed 200. A net-

work could have up to 10 EZ-ZONE controllers with

20 members each maximum or the 200 members

can be divided any way the user would like as long

as 20 I/O members per controller are not exceeded.

Using the graphic below as an example, if [Gtw]

instance 1 - 4 has [ao;nb] and [ai;nb] set to 5, each

of the four EZ-ZONE family controllers will contain

the first 5 members of the assembly and this informa-

tion would then be passed implicitly to the Master on

the DeviceNet™ network. The EDS (Electronic Data

Sheet) can be found on the CD shipped with the prod-

uct "Controller Support Tools".
Note:

To minimize traffic and enable better throughput

on Standard Bus, set the End Zone prompt [nU;2n]

in the RUI to the maximum number of EZ-ZONE

controllers on the network to be scanned.

DeviceNet RUI/GTW LED Indicators

Viewing the unit from the front and then looking on

top of the RUI/GTW two LEDs can be seen aligned

vertically front to back. The LED closest to the front

is identified as the network (Net) LED where the one

next to it would be identified as the module (Mod)

LED.

Network Status (NS)

Indicator LED Description

Off

The device is not online and has not com-

pleted the duplicate MAC ID test yet. The

device may not be powered.

Green

The device is online and has connections in

the established state (allcated to a Master).

Red

Failed communication device. The device

has detected an error that has rendered it

incapable of communicating on the network

(duplicate MAC ID or Bus-off).

Flashing Green

The device is online, but no connection has

been allocated or an explicit connection has

timed out.

Flashing Red

A poll connection has timed out.

Module Status (MS)

Indicator LED

Description

Off

No power is applied to the

device.

Flashing Green-Red

The device is performing a

self-test.