beautypg.com

Cip - communications capabilities, Watlow ez-zone, Rui/gateway – Watlow EZ-ZONE RUI/Gateway User Manual

Page 35

background image

Watlow EZ-ZONE

®

RUI/Gateway

32

Chapter 5 Networking with a Gateway

Assembly Definition Addresses

- Fixed addresses used to define the parameter that

will be stored in the "Working Addresses", which

may also be referred to as a pointer. The value

stored in these addresses will reflect (point to) the

Modbus address of a parameter within the con-

troller.

Assembly Working Addresses

- Fixed addresses directly related to their associated

Assembly Definition Addresses" (i.e., Assembly

Working Addresses 200 & 201 will assume the the

parameter pointed to by Assembly Definition Ad-

dresses 40 & 41).

When the Modbus address of a target parameter is

stored in an "Assembly Definition Address" its cor-

responding working address will return that parame-

ter’s actual value. If it’s a writable parameter, writing

to its working register will change the parameter’s

actual value.

As an example (using the EZ-ZONE ST Users

Guide), Modbus register 360 and 361 (Map 2) con-

tains the Analog Input 1 Process Value (See Opera-

tions Page, Analog Input Menu). If the value 360 and

361 is loaded into Assembly Definition Addresses 90

and 91, the Process Value sensed by Analog Input 1

will also be stored in Modbus registers 250 and 251.

Note that by default this parameter is also stored in

working registers 240 and 241 as well.

Note:

When changing the assembly as in the example

above a multi-write function must be used, i.e.,

writing 360 to register 90 and 361 to register 91. All

members in the assembly are 32 bits.

The table identified as " Modbus Programmable

Memory Blocks" found in the appendix of this Users

Guide reflects the assemblies and their associated ad-

dresses.
To learn more about the Modbus RTU protocol point

your browser address below:

http://www.modbus.org

Note:

To minimize traffic and enable better throughput

on Standard Bus, set the Number of Zones prompt
[nU;2n]

in the RUI to the maximum number of EZ-

ZONE controllers on the network to be scanned.

Note:

The logic used when determining the Modbus offset

is based on the number of Modbus addresses need-

ed for any given controller. In the above example,

each PM controller would have access to the first

5000 Modbus registers (400001 - 405001).

Note:

If using a legacy EZ-ZONE ST controller with a

firmware version less the 3.0, consider using the

Modbus addresses listed in the ST Users Guide

in the column entitled "RUI/GTW Modbus". If the

firmware in the ST is 3.0 or higher new features

were added and made accessible through the Map

2 registers. If interested in using the new features

today or perhaps in the future configure the ST for

Map2 Modbus registers.

CIP - Communications Capabilities

Communications using CIP (EtherNet/IP and De-

viceNet) can be accomplished with any EZ-ZONE con-

troller using an RUI/GTW. Reading or writing when

®

[gtW]

1 = PM1

[gtW]

4 = PM4

Baud Rate

[baud]

= 9.6, 19.2, 38.4Kb

[Com]

Instance 2

Parity

[par]

= [none], [euen], [odd]

Modbus

®

RTU

Watlow Standard Bus

(Daisy chain EIA-485)

EZ-ZONE

®

Controllers

1 - 16 maximum

Modbus

®

Offset

* 15000

Modbus

®

Offset

* 10000

Modbus

®

Offset

5000

Modbus

®

Offset

0

* The RUI allows for a maximum entry of 9999 due to the limitations of the 7 segment display. To enter an offset > 9999

EZ-ZONE

®

configurator software must be used.

Modbus

®

Address

[ad;m]

= 1 - 247

Modbus

®

Word Order

[M;hl]

= [lohi] or [hilo]

[Com]

Instance 1

Standard Bus Address

[Ad;S]

= 1-8

Start Node to Scan

[St;2n]

= 1-24

End Zone to Scan

[nU;2n]

= 1-24

RUI/Gateway

Setup Prompts

[gtW]

= 1 – 16

(Gateway Instance)

[Du;En]

= Yes or No

(Enable gateway instance)

Gateway

[Du;st]

= [On] or [off]

(Device Status)

[M;of]

= 0 – 65535

*

(Modbus

®

Offset)

Units

[`C_f]

= [``f] or [``C]