ST3000 Series Hardware Manual

4-12

4.2.2

Connecting the Power Supply

This section describes the precautions for supplying a power voltage.

• If the supplied voltage exceeds the ST unit’s range,

connect a constant voltage transformer.

• Between the line and ground, select a power supply that

is low in noise. If there is an excess amount of noise,

connect a insulating transformer.

• When supplying power to the ST unit, be sure to

separate the input/output and power lines, as shown.

• To increase the noise resistance quality of the power

cord, simply twist each power wire before attaching the

Ring Terminal.

• The power supply cable must not be bundled or

positioned close to main circuit lines (high voltage, high

current), or input/output signal lines.

• Connect a lightning surge absorber, as shown in the

diagram, to deal with power surges.

• To avoid excess noise, make the power cord as short as

possible.

• DC24V input unit is must be used with a Class 2 power

supply.

SEE

Chapter 3 Specifications (page 3-1)

• Use constant voltage and

insulating transformers with

capacities exceeding Power

Consumption value.

• Be sure to ground the surge

absorber (E1) separately from the

ST unit (E2).

• Select a surge absorber that has

a maximum circuit voltage greater

than that of the peak voltage of

the power supply.

ST

ST Power

Input/Output

Power

Main Power

ST

Main Circuit

Lightning Surge

Absorber

ST

E2

FG

E1

Constant

Voltage

Transformer

Twisted-pair cord

ST

FG

Insulating

Transformer

T2

T1

Twisted-pair cord