Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 104
Chapter 5 Maintenance
5-5
• The gasket must be inserted correctly into the groove for the ST’s moisture
resistance to be equivalent to IP65f.
• Since the gasket is flexible but not elastic, be careful not to stretch it
unnecessarily, as doing so could tear the gasket.
• Be sure the gasket’s seam is not inserted into any of the unit’s corners, only in
the straight sections of the groove. Inserting it into a corner may lead to its
eventually tearing.
• To ensure stable resistance against dust and moisture, insert the gasket so that
the seam is at the bottom of the ST unit.
• The upper surface of the gasket should protrude approximately 2.0mm[0.08in]
out from the groove. Be sure to check that the gasket is correctly inserted before
installing the ST into a panel.
2.0mm[0.08in]
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"