Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 41
ST3000 Series Hardware Manual
3-10
Serial Interface (COM2)
This interface is used to connect an RS-485 (MPI only) serial cable. A D-Sub 9-pin socket connector is used.
ST Connector
XM3B-0942-502LX
Interfit Bracket
#4-40 inch screws are used.
Recommended Cable Connector
XM2A-0901
Recommended Cable Cover
XM2S-0913
Recommended Jack Screw
XM2Z-0073
Pin
Arrangement
Pin No.
RS-485 (MPI only)
Signal Name
Direction
Meaning
1
NC
-
-
2
NC
-
-
3
LINE(+)
Input/
Output
LINE(+)
4
RS(RTS)
Output
Request to Send
5
SG
-
Signal Ground
*1
*1.
The SG and FG terminals are isolated.
6
5V
-
5V External Output
*2
*3
*2.
The 5V output for Pin # 6 is not protected against overcurrent. To prevent damage or
unit malfunctions, use only the rated current.
*3.
When providing power via the Siemens Co.’s PROFIBUS connector, power cannot
be connected to the Device/PLC.
7
NC
-
-
8
LINE(-)
Input/
Output
LINE(-)
9
NC
-
-
Shell
FG
-
Frame Ground
*1
(Common with SG)
9
6
5
1
(ST unit side)
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"