6 setting – IAI America PCON-CFA User Manual

Page 24

background image

2. ACON-C/CG,

PCON-C/CG


18

CompoNet

2.6 Setting

2.6.1 Operation

Mode

Selecting


The operation mode is set using the parameters.
Set the mode toggle switch on the front surface of the controller to “MANU” side and set the parameter No. 84
“FMOD: Field Bus Operation Mode” using the RC PC software (V6.00.08.00 or later). (Refer to 2.10, "CompoNet
Related Parameters”.)

Set Value

Operation Mode

Number of

occupied bytes

0 (Factory setting)

Remote I/O Mode

2

1

Position / Simplified Direct

Value Mode

8

2

Half Direct Value Mode

16

3

Full Direct Value Mode

32

4

Remote I/O Mode

12

* Entering any value except for the ones described above will cause an “Excessive Input Value Error”.



2.6.2 Station

No.

Setting


The node address is set by the parameters.
Set the parameter No. 85 “NADR: Field Bus Node Address” using the RC PC software.
(Refer to 2.10, "CompoNet Related Parameters”.)

Settable Range:0 to 63 (It is set to “0” when the machine is delivered from the factory.)



(Note)

Exercise caution to avoid node address duplication.
The nodes (controllers) are assigned in the order of their node address in the remote I/O address
areas of the PLC.
For details, refer to the Operation Manuals of the master unit and PLC in which in the master unit is
installed.


(Note)

The setting for the communication speed is not required because it automatically follows the master’s
communication speed.


(Note)

After the parameter setting, turn on the power to the controller again and return the mode toggle switch
on the front of the controller to “AUTO” side.
When the switch is set to “MANU”, the operation using PLC is not available.