IAI America PCON-CFA User Manual
Page 124
3. SCON-CA/CF
A
118
CompoNet
(3) I/O signal assignment
(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)
Signal Type
Bit
Symbol
Contents
Details
Target
Position
32-bit
data
-
32-bit signed integer indicating the current position
Set the target position on the absolute coordinates.
The unit is 0.01mm and settable range is–999999 to +999999.
(Examle) When it is “+25.41mm”, set it as “2541”.
If the value larger than the value (0.2mm) inside the soft limit for
the parameter, the movement would be limited to the inside the soft
limit (0.2mm).
* When the input is performed in hexadecimal notation, input the
negative value using a complement of 2.
3.9 (3)
Positioning
Band
32-bit
data
-
32-bit integer
The unit is 0.01mm and settable range is 1 to +999999.
(Example) When it is “25.40mm”, set it as “2540”.
This register value has two meanings depending on the operation
type.
1) In the case of positioning operation, it shows the allowable range
from the target position, that is regarded as the positioning
completion.
2) In the case of pressing operation, it shows the pressing width
value. Specify the normal operation or pressing operation using
the “PUSH” control signal setting.
3.9 (3)
Velocity
32-bit
data
-
32-bit integer
Specify the speed at which to move the actuator.
The unit is 0.01 mm/sec and the settable range is 0 to 999999.
(Example) When it is “25.41mm/sec”, set it as “2541”. When the
movement command is set with the value bigger than the max.
speed, an alarm is issued.
3.9 (3)
PLC Output
Zone boundary+
/Zone
boundary–
32-bit
data
-
32-bit signed integer indicating the current position
After completion of home return, an effective zone signal can be
output separately from the zone boundaries specified by
parameters.
The status signal PZONE turns ON when the current position is
inside these +/- boundaries. (Example) When it is “+25.40mm”, set
it as “2540”.
The unit is 0.01mm and the settable range is -999999 to 999999.
Enter a value that satisfies the relationship of “Zone boundary + >
Zone boundary –
̍.
If this function is not used, enter the same value for both the
positive and negative boundaries.
*When the input is performed in hexadecimal notation, input the
negative value using a complement of 2.
3.9 (3)