RMA-303 Dual Purge/Direct Charge - Installation

40

INTERLOCKS

The following system interlocks are required to

prevent equipment damage:

1. Bearing air should remain on at all times and

should be shut off only by turning off the mainair

to the pneumatic control cabinet.

C A U T I O N

!

†

Bell cup must be rotating at least 20,000

rpm when fluid is triggered. Turning on fluid

without the bell cup spinning may flood the

turbine and cause damage to components.

C A U T I O N

!

†

When the turbine air is turned off, the tur-

bine will continue to operate or "coast down"

for about two minutes. Provisions should be

made to assure that the operator waits at least

three minutes, after shutting off the turbine air

and before shutting off the main air supply.

†

The bell cup must be removed when

making flow checks. If the paint is turned on

when the bell is mounted and the turbine shaft

is not rotating, paint will enter the shaft and

possibly damage the air bearing. Material

flow checks (flow rate verification) must be

made with the bell cup off and the turbine

not rotating. Normally pneumatic interlocks

will not allow the paint to trigger on when the

turbine air is off. These interlocks may need

to be bypassed with proper safety procedures

as required.

2. It should not be possible for the coating ma-

terial to be sprayed unless the turbine is spin-

ning.

3. Two interconnected bearing air ports are provid-

ed, one for supply air and the other to be used

as a return signal for measuring bearing air

pressure at the atomizer. If bearing air falls

below 80 psi (551.6 kPa) at the atomizer, the

turbine air should be automatically interlocked

to shut off. This interlock is provided by the

Serial Atomizer Module (see current "Serial

Atomizer" manual).

4. High voltage must be interlocked with the

solvent valve pilot signal to prevent solvent flow

while high voltage is energized.

Ransburg

LN-9263-08.5

†

Never spray solvent with high voltage on.

W A R N I N G

!

†

Under normal operation, the high volt-

age and/or coating material must never be

turned on unless the bell cup is mounted on

the motor shaft and the turbine is rotating.

†

Pneumatic input to the turbine air

inlet must be controlled to prevent the

turbine from exceeding the maximum

rated speed of 70,000 rpm. (See "Spec-

ifications" in the "Introduction" section.)

†

High voltage must never be turned on

while cleaning solvent is being sprayed either

through the applicator supply or the cup wash

line. High voltage and both solvent triggers

must be interlocked.

W A R N I N G

!

5. Turbine air and brake air must be interlocked

to

prevent both from being used simultaneously.

This interlock is provided by the Serial Atomizer

Module (see current "Serial Atomizer"manual).

6. Any other interlocks required by local code,

national code, or international code.

7. High voltage must be interlocked with the

booth entry door.