beautypg.com

Ransburg, Rma-303 dual purge/direct charge - installation – Ransburg RMA Dual Purge Direct A12300 User Manual

Page 38

background image

RMA-303 Dual Purge/Direct Charge - Installation

33

Where items are mounted directly on structural

components such as building columns, the ground

connection MUST still be made. In many cases

the structural component may be painted or coat-

ed with an insulated material and in all cases the

Ransburg equipment will be painted. These coat-

ings are insulating. The ground connection must

be as perfect as possible. The indicated ground

terminal on the Ransburg equipment will provide

the necessary connection at on end, but the user

must be sure that the other end is secured to an

earth ground. This may be achieved by the use of

a standard ground clamp (properly secured), by

brazing or by piercing the structural component

enough to assure connection. All ground con-

nections should be made to the most conductive

metallic structural ground available.

To be sure that everything is properly grounded,

the following steps should be undertaken at least

daily:

1. Inspect all ground wires. Look for good, firm

joints at all points of connection. Look for breaks in

the ground wire. Repair all defects IMMEDIATELY!

2. Inspect the floor or grates for excessive accu-

mulation of dried coating material or other residue.

If there is any, remove it!

†

Ransburg recommend that ground

connections to earth ground be 3/4-inch

insulated copper braided wire. Grounds

between assemblies within a machine

should be ran to a central point within the

machine using #18 insulated stranded

copper wire minimum. All connections

should be mechanically sound and have

less than five (5) ohms of resistance be-

tween assemblies and the common point.

The resistance between the central point

and earth ground should be less than five

(5) ohms as well.

NOTE

Safe Grounding is A Matter of

Proper Equipment Maintenance

and Installation, Correct Operation

and Good Housekeeping

Daily inspection of grounding apparatus and con-

ditions, however, will help prevent hazards that

are caused by normal operations.

BE SURE THAT:

1. All objects in the spray area are grounded.

2. Personnel in the spray area are properly ground-

ed. (Conductive safety shoes, and coveralls.)

3. That the target object is properly grounded (less

than 1 megohm resistance).

4. That the high voltage is off except during nor-

mal application.

5. That the high voltage is off and applicators are

grounded during maintenance operations.

6. The spray area is kept free of accumulated

coating deposits.

7. All combustible liquids in the spray area (outside

of automatic delivery systems) are kept to minimum

and are kept in fire safe, grounded containers.

(See NFPA-30 and chapter 6 of

NFPA- 33.)

8. Proper ventilation is provided.

9. Personnel must thoroughly understand the

equipment, its operation and maintenance, and

all safety precautions.

Ransburg

LN-9263-08.5