beautypg.com

Pic statement, Pic s – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 62

background image

DIN-MON™ SMART METER

62-0442—04

62

PIC S

TATEMENT

BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

Vendor Name:

E-Mon

Vendor ID:

482

Product Name:

Din-Mon™ Meter

Product Model Numbers:

D2 Smart Meter, D5 Advanced Smart Meter

Product Description

Kilo-watt hour meter

BACnet Standardized Device Profile (Annex L):
X

BACnet Smart Sensor (B-SS)

BACnet Interoperability Building Blocks Supported (Annex K):
X

K.1.2 BIBB - Data Sharing - ReadProperty-B (DS-RP-B)

X

K.1.4 BIBB - Data Sharing - ReadPropertyMultiple-B (DS-RPM-B)

X

K.5.2 BIBB - Device Management - Dynamic Device Binding-B (DM-DDB-B)

X

K.5.4 BIBB - Device Management - Dynamic Object Binding-B (DM-DOB-B)

Segmentation Capability:
None

Standard Object Types Supported
X

Device Object

X

Analog Input

For all these properties, the following apply:
1.

Does not support BACnet CreateObject

2.

Does not support BACnet DeleteObject

3.

No additional writable properties exist

4.

No proprietary properties exist

5.

No range restrictions exist

Data Link Layer Options:
X

MS/TP master (Clause 9), baud rate(s): 9.6k, 19.2k, 38.4k, 76.8k bps

X

BACnet IP, (Annex J): Din-Mon™ D2 meter does not support BACnet IP

Device Address Binding:
Not supported

Character Sets Supported:
X

ANSI X3.4