beautypg.com

8 wiring the communications, 1 rs-485 network and wiring – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 29

background image

DIN-MON™ SMART METER

29

62-0442—04

4.8 Wiring the Communications

4.8.1 RS-485 Network and Wiring

RS-485 communication allows a computer, automation system, or

modem to communicate with one or more Din-Mon™ meters. You can

connect as many as 52 meters along a 4,000-foot RS-485 cable run

with Belden 3106A cable or equivalent. The cable rating of 600V allows

the RS-485 network to be used in cabinets with service voltage up to

600V. Meter is supplied with internal bias of Belden 3106A 45K Ohms, some

installations may require additional biasing. A typical RS-485 network requires the use

of one 120 Ohm termination resistor at each end of the RS-485 cable run. The

termination resistors are installed across the ‘+’ (high) and ‘–’ (low) terminals.

Din-Mon™ meter supports 3 protocols on RS-485 connection operating in half-duplex,

stop-and-wait mode. They are available in Modbus RTU, BACnet MS/TP, or EZ7.

The Din-Mon™ meter RS-485 network uses the convention ‘+’ and ‘–’ to represent the

lines ‘A’ and ‘B’, defined by the RS-485 standard, respectively; in addition, “SC” is used

for signal common.

The daisy-chain topology is used to link multiple meters together for one connection

back to the computer, automation system, or modem.

Fig. 23. A 3-Wire RS-485 Network Diagram.

NOTE: Belden 3601A recommended for RS-485 up to 600V environment appli-

cations. Torque screws to 2 in-lbs.

M35109

BELDEN 3106A

M35156

SC LINE

– LINE
+ LINE

SC – +

SC – +

SC – +

120 OHM TERMINATION RESISTORS SHOULD BE INSTALLED ACROSS + (PLUS) AND – (MINUS)

AT THE BEGINNING AND END OF THE RS-485 NETWORK.

1

TERMINATION

RESISTOR

SH (SHIELD)

TERMINATION

RESISTOR

1

1