3.2 Communication Ports and Output Contact

Terminals

The Communication Ports and Output Contact Terminals are located along the top

edge of the meter.

Fig. 7. Communication Ports and Terminals.

The VAR-Hour/Phase Loss and Watt-Hour pulse output terminals provide a scaled

VAR-Hour/Watt-Hour pulse that is dependent on the meter amperage rating. Please

see Section “Pulse Type and Value” for pulse values. Optionally the VAR-Hour

terminals can be set to indicate a “Loss of Phase” alarm output.

The VAR-Hour/Phase Loss and Watt-Hour pulse output terminals are solid-state

switches. Switching is limited to 100mA (0.1 Amp) and voltage should not exceed 60

Volts AC or DC.

One 3-terminal screw terminal plug is provided for RS-485 communications.

Din-Mon™ D5 meters are available with a RJ-45 jack for 10/100-Base-T Ethernet for

communicating via Modbus TCP/IP, BACnet IP, or EZ7 over Ethernet. Ethernet is not

available on the Din-Mon™ D2 meters: if the meter was ordered with LonWorks, a z-

position screw terminal plug for LonWorks will replace the RJ-45 jack (Ethernet).