DIN-MON™ SMART METER

27

62-0442—04

4.7 Installation Diagnostics

Following is a list of diagnostic messages that may appear on the meter display.

DIAGNOSTIC MESSAGES SHOULD NOT BE ON CONTINUOUSLY WHEN THE

METER IS INSTALLED PROPERLY AND IS IN WORKING ORDER.

4.7.1 Line Voltage Diagnostics

The diagnostics program detects line voltage faults by displaying one of two

messages:

Error Messages:

PH Seq Err

PH Loss C

PH Seq Err indicates that the 3-phase line voltage is not hooked up in the proper

phase sequence. This message should never be seen continuously on the display

during normal operation. The meter will not display correct electrical data in this

condition. The phase sequence error must be remedied in order for the meter to work

properly.

PH Loss C indicates that the line voltage is missing on Phase C. This message will

appear whenever the power on Phase C is off.

4.7.2 Current Sensor Diagnostics

The load current must be at least 1% of the meter’s rated load in order to use the

diagnostic function.

Current sensor diagnostics can detect:

1. Reversed current sensors

2. Incorrect phase correspondence

Error Messages:

CT Err A

CT Err A B

CT Err A C

CT Err: (ABC) is used to detect the swapping or mis-wiring of current sensor

phases.