4.5 Wiring Current Sensor Inputs

Once the AC voltages have been confirmed to be within acceptable limits, you are

ready to install the current sensors. De-energize the meter for this procedure. In the

lower right corner of the meter are the sensor connection terminals. Each sensor

connects to two terminals, one labeled “WHT” for white and the other “BLK” for black.

Positions 1 and 2 are the inputs for Phase A sensor, positions 3 and 4 are the inputs

for Phase B sensor and positions 5 and 6 are the inputs for Phase C sensor; torque

screws to 2 in-lbs.

Fig. 13. Current Sensor Input Terminals (front view).

The Din-Mon

TM

meter is available for use with voltage (0.333V) output type of sensors

or with current (100mA) output type of sensors.

NOTE: The sensor output type is indicated in the part number (OS) as “V3” for

0.333V and “C1” for 100mA type.

Each output type is available in two forms:

1. Split-core current sensor. This sensor opens so that it can be attached around

the circuit being monitored without disconnecting the conductors.

2. Solid-core current sensor. This sensor does not open and requires the monitored

conductor to be removed from the circuit to install the current sensor.

NOTE: UL Current Sensors rated for Measurement Category III providing dou-

ble insulation for 600V installations.

CURRENT SENSOR INPUTS

M35101

SENSOR 1

TERMINAL

POSITIONS 1-2

SENSOR 2

TERMINAL

POSITIONS 3-4

SENSOR 3

TERMINAL

POSITIONS 5-6