MOD 30ML Display Guide

Application Examples

5 - 42

Each display block to be scrolled must have its own input to the expression block. The
highest value of DISPLAYS will be one less than the total number of displays to be scrolled.

The Result of the Expression block is configured as Count with an initial value of 1.

The result of the Expression Block is also connected to the Remote Display Input of the
Display interface (DIF) Block.

Finally, the Scan Group in the Interface Block must be set to allow a reasonable viewing
period of each display before changing to the next one. If the display blocks are in Group 1
and the Group 1 Scan Rate is set to 2 seconds, the displays will scroll at that rate.