beautypg.com

Micromod MOD: 30ML Display Script Guide User Manual

Page 36

background image

MOD 30ML Display Guide

Display Basics

2 -30

Figure 2 .25.

Display Block
Formats – Clear
Totalizer

17. Connect from Clear of the Display Block,

to the RESINP input of the TOT block

This seems as though it is backward, but
actions from the front panel are
connected in this manner.

18. Close the loop compound.

19. At the top level of the strategy, open the

State Table (ST) block

20. Select the Tables tab

21. Scroll to the bottom of the State Table list.

22. Leave one line after the last entry and add

the following EXACTLY AS IT APPEARS
BELOW:

clear, 3, “???”
{
1, “YES”;
0, “NO”;
}

The name of the state table is clear (this
was entered in the Format list of the
Display block; it is case sensitive).
The maximum number of characters to
be displayed is 3.
If the instrument firmware returns none of
the correct codes, ??? will be displayed.
When the arrow keys are pushed a count
of 0 or 1 is sent. If the count is 1, YES
will be displayed. If the count is 0, NO
will be displayed. The operator must
then press the flashing ENT key for YES
or NO to be accepted by the instrument.

23. Close the ST block using the OK button

When the strategy is compiled and downloaded, the totalizer immediately begins to count.
When the UP or DOWN arrow is pressed from the STM TOT display, YES appears on
Line 6. Pressing the flashing ENT key clears the totalizer and the count immediately
begins again.