6.1 1601 Circuit Board Description and Adjustments

SECTION 6 - ADJUSTMENTS

The switch settings and adjustments in this chapter should be made after your installation and wiring to the operator is
complete. Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and then
turned back on for the new setting to take effect.

Auto close timer (when
turned on) SW 1, switch 7.

Adjust from 1 second (full
counter clockwise) to
approximately 59 seconds
(full clockwise).

SW 1

Dual Channel Loop Detector

Single Channel Loop Detector

Up Limit LED
Down Limit LED

Limit
Sensor

See page
25.

1

59

Down T

erminals

Up T

erminal

Auto Close Timer

(C – NC – NO) This relay can be used for a
variety of purposes and is typically used to
signal when the arm is up or down.

Arm Relay Contacts

An automatic sensor
system that senses
entrapment of a solid
object and is incorpo-
rated as a permanent
and integral part of the
operator.

Gate Tracker

Activity LED

Operator status
reporting; cycle count,
shorted inputs, loop
detector problems,
power interruptions, etc.
See page 11.

Gate Operator
Data Terminal

Adjust reversing
sensitivity for the
DOWN direction of
arm.
See page 25.

Min

Max

Reverse Sensor

1

ON

2

3

4

5

6

7

8

Self test (when
turned on) SW
1, switch 2.

SW 1

Self Test

1

ON

2

3

4

5

6

7

8

Relay activation is

dependant on

setting of SW 1,

switch 5.

Dry relay contacts (terminals 12-13) can be
set for Normally Open (NO) or Normally
Closed (NC) operation by placing the relay
shorting bar on the N.O. or N.C. pins
respectively. See page 10 and next page.

N.C.

N.O.

SW 1

Dry Relay Contact

1

ON

2

3

4

5

6

7

8

Set the DIP-switches on
the circuit board to the
desired setting. See
switch settings informa-
tion on the next 3 pages.

Note: SW 2, switch 1
MUST be set for the
correct model operator
that has been installed.

SW 1

SW 2

DIP-Switches

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

941

DoorKing Plug-In

Loop Detectors

(Sold separately)

P

601

Power

LED

N

Input LEDs

How LEDs Function

Illuminated LEDs Indicates that
low voltage power is being
applied to the circuit board.

Input LEDs should be OFF and will
only illuminate when the input is
activated.
Limit LEDs will only illuminate when
the respective limit sensor has been
activated.