6.1 1601 Circuit Board Description and Adjustments
SECTION 6 - ADJUSTMENTS
The switch settings and adjustments in this chapter should be made after your installation and wiring to the operator is
complete. Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and then
turned back on for the new setting to take effect.
Auto close timer (when
turned on) SW 1, switch 7.
Adjust from 1 second (full
counter clockwise) to
approximately 59 seconds
(full clockwise).
SW 1
Dual Channel Loop Detector
Single Channel Loop Detector
Up Limit LED
Down Limit LED
Limit
Sensor
See page
25.
1
59
Down T
erminals
Up T
erminal
Auto Close Timer
(C – NC – NO) This relay can be used for a
variety of purposes and is typically used to
signal when the arm is up or down.
Arm Relay Contacts
An automatic sensor
system that senses
entrapment of a solid
object and is incorpo-
rated as a permanent
and integral part of the
operator.
Gate Tracker
Activity LED
Operator status
reporting; cycle count,
shorted inputs, loop
detector problems,
power interruptions, etc.
See page 11.
Gate Operator
Data Terminal
Adjust reversing
sensitivity for the
DOWN direction of
arm.
See page 25.
Min
Max
Reverse Sensor
1
ON
2
3
4
5
6
7
8
Self test (when
turned on) SW
1, switch 2.
SW 1
Self Test
1
ON
2
3
4
5
6
7
8
Relay activation is
dependant on
setting of SW 1,
switch 5.
Dry relay contacts (terminals 12-13) can be
set for Normally Open (NO) or Normally
Closed (NC) operation by placing the relay
shorting bar on the N.O. or N.C. pins
respectively. See page 10 and next page.
N.C.
N.O.
SW 1
Dry Relay Contact
1
ON
2
3
4
5
6
7
8
Set the DIP-switches on
the circuit board to the
desired setting. See
switch settings informa-
tion on the next 3 pages.
Note: SW 2, switch 1
MUST be set for the
correct model operator
that has been installed.
SW 1
SW 2
DIP-Switches
1
ON
2
3
4
5
6
7
8
1
ON
2
3
4
5
6
7
8
941
DoorKing Plug-In
Loop Detectors
(Sold separately)
P
601
Power
LED
N
Input LEDs
How LEDs Function
Illuminated LEDs Indicates that
low voltage power is being
applied to the circuit board.
Input LEDs should be OFF and will
only illuminate when the input is
activated.
Limit LEDs will only illuminate when
the respective limit sensor has been
activated.