beautypg.com

3 connecting the frame and reference grounds – Alpha Technologies Cordex CXPS-M 48_24-1200_600A User Manual

Page 42

background image

9400004-J0 Rev B

40

6.3 Connecting the Frame and Reference Grounds

CAUTION!

The grounding methods described in this section are generic. Follow local requirements
and electrical code.

NOTE:

This power system is suitable for installation as part of a Common Bonding Network

(CBN) and is intended to be used in a DC-C configuration (common DC return).

A true single point ground system means that everything is referenced to a single point that is tied to the external

earth ground system. In reality each component and external source is effectively bonded to a single point, which

is then effectively bonded to the facility or site external ground system.

6.3.1 Connecting the power plant battery return reference lead

1. Connect the isolated power system battery return bus (BRB) to the building master ground bus (MGB) or

floor ground bus (FGB) in larger buildings (Figure 23). This acts as a system reference and a low impedance

ground path for surges, transients, noise, etc. The MGB or FGB should have a direct low impedance path to

the building grounding system.

2. Size the cable between the power system and the MGB or FGB so that there is sufficient ampacity to clear

the largest fuse or breaker on the power system, excluding the battery protection fuse or circuit breaker—see

Table G on page 41. This is the minimum requirement for these high capacity plants. Other factors, including

length of cable and special grounding requirements of the load, must be factored in. The insulated cable

should be equipped with two-hole crimp type lugs and should not have any tight bends or kinks.

Figure 23 —

Frame and reference returns (front view)

MGB or FGB

BRB

CXPS power

system bay

Battery rack

Battery rack

Frame
ground

To site
ground

Optional external battery plant

This manual is related to the following products: