25

9400004-J0 Rev B

Relays

Digital Inputs

I/O and Alarm

Interface

board

Cordex

Controller

board

LCD

Display

board

3.12.1 Control Cards

The control cards are mounted inside the door of the controller distribution module (Figure 16).
The CXCP can accommodate up to eight digital input channels. These channels can monitor digital alarm/control

signals from rectifiers, converters and other types of equipment. Some of these channels are pre-assigned to

monitor specific signals. See the Software manual for more information.
Each CXCP contains eight standard and eight optional Form C alarm output relays to extend alarms and control

external apparatus. Each internally generated alarm or control signal may be mapped to any one of the 16 relays,

or, several signals may be mapped to just one relay or none at all.
Refer to the detailed as-built schematic that ships in your documentation package.

Figure 16 — Control cards