Figure 4 — 1200a dual voltage system – Alpha Technologies Cordex CXPS-M 48_24-1200_600A User Manual

Page 17

background image

15

9400004-J0 Rev B

3.5.2 DC Charge Buses - Dual Voltage

Dual voltage systems have three vertical charge bars:
• One connecting all of the return terminals
• One busbar connecting all the "hot" terminals of the rectifier shelves and the input to the converter shelf–rat-

ed for the maximum 1200A current.

• The third bus bar delivers secondary voltage from the converters to the load–rated to 600A.

Figure 4 —

1200A dual voltage system

Secondary

voltage bus

Primary

voltage bus

Common

return bus