5.3 Mounting the External Battery Return Bus Bar (Optional)
An external battery return bus bar kit (part number 7400250-001) is available to make the battery return connec-
tions for the loads and to serve as the common connecting points for the positive side of the bay and the batter-
ies.
Each bar has a 2500A capacity.
1. Before joining ground bar components together, ensure that all contact surfaces on the busbars are clean
and coated with a thin coat of NO-OX-ID “A” compound (or approved equivalent).
2. Assemble and mount the kit on a customer supplied auxiliary framing superstructure away from the system.
Customer supplied auxiliary
frame (2 " x 9/16")
Figure 19 —
External battery return bus bar kit (2 bars shown)
47.75"
6.00"