Serial communications points – Bell & Gossett S14367B Technologic Constant Speed Pump Controller User Manual
Page 38

Technologic
®
Constant Speed Pump Controller Installation, Operation and Maintenance Manual
38
Serial Communications Points
Description
Read
Write Range/Value
Modbus
Bacnet
Lonworks
N2
Address
Address NV Index Address
Pump2 State
X
0=Disabled, 1=Run, 2=Ready, 30002
AI 2
45
ADI 2
3=Failed
Pump3 State
X
0=Disabled, 1=Run, 2=Ready, 30003
AI 3
46
ADI 3
3=Failed
Pump4 State
X
0=Disabled, 1=Run, 2=Ready, 30004
AI 4
47
ADI 4
3=Failed
Pump5 State
X
0=Disabled, 1=Run, 2=Ready, 30005
AI 5
48
ADI 5
3=Failed
Pump6 State
X
0=Disabled, 1=Run, 2=Ready, 30006
AI 6
49
ADI 6
3=Failed
Suction/Return Pressure
X
X*
0-Span
30007/
AI 7/AO 1
50/63
ADI 7
40001
System/Supply Pressure
X
X*
0-Span
30008/
AI 8/AO 2
51/64
ADI 8
40002
Flow
X
X*
0-Span
30009/
AI 9/AO 3
52/65
ADI 9
40003
Temperature (4-20mA)
X
X*
0-Span
30010/
AI 10/AO 4
53/66
ADI 10
4004
Pressure
X
X*
0-Span
30011/
AI 11/AO 5
54/67
ADI 11
4005
Differential Temperature
X
X*
0-Span
30012/
AI 12/AO 6
55/68
ADI 12
4006
Suction/Return Temp (RTD)
X
Actual °F
30013
AI 13
56
ADI 13
System/Supply Temp (RTD)
X
Actual °F
30014
AI 14
57
ADI 14
Amps
X
Actual Amps
30015
AI 15
58
ADI 15
Horsepower
X
Actual Horsepower
30016
AI 16
59
ADI 16
* “AI Ovrd” must be set to “Y” for the corresponding sensor type in the communications setup screen in order to be writable.
See section 4.3.10.5 for more information on analog input override.