Operation

Variable

Units Description

HP

Horse- Total power measured by

power the power module

Volts

Volts

Average voltage measured by

the power module

Amps

Amps Total current measured by the

power module

PF

N/A

Power factor measured by the

power module

Table 9: Power Variables

3.4.7

Optional Sensors

Pressing NEXT, the controller will display the

Optional Sensors screen shown below if any optional
sensors are set up. If they are not, the Optional

Sensors screen will be skipped. See section 4.1 for

information on sensor setup.

OPTIONAL SENSORS

Temp =### Flow=#####

Diff Temp= ###

Pressure = ### Alm

Variable

Units Description

Temp

°F

Optional temperature

Diff Temp

°F

Optional differential

temperature

Pressure

PSI

Optional pressure

Flow

GPM Optional flow

Table 10: Optional Sensor Variables

3.5

Alarms/Events

Some conditions can be defined as alarms or events,

while others are predefined to be alarms. See section
4.5 for alarm setup. Alarms are logged in the Alarm

Log and events are logged in the Events Log. See sec-
tion 4.7 for logging. An alarm triggers the General

Alarm serial communications point and the A/V

Alarm relay output. An event will not trigger either
of these. See Appendix C for the serial communica-

tions points list and section 4.3.8 for relay outputs
setup.

Some alarms or events will cause one or all of the
pumps to shut down. For Low System Pressure, the

user can define if the pumps will shut down or not.

All alarms or events require either a manual or auto-

matic reset. The RESET/SILENCE LED will flash

when a manual reset is required. Press the RESET key
to manually reset the system.

The values in parentheses in Table 11 are the default

values.