Technologic

®

Constant Speed Pump Controller Installation, Operation and Maintenance Manual

15

From the status screens, shown in section 3.4, press

the SETUP key to get to the Setup Menu shown
below. Field values columns are provided to record

user setup information for future reference. For the
remainder of this manual, the path to navigate to a

particular screen will be given as follows: Path: Status

Screens/Setup(3).

Setup Menu: # 0=Exit

1=Sensors 4=Test

2=Pumps 5=Alrm/Evt

3=System 6=EZ-Start

4.1

Sensor Setup

Path: Status Screens / Setup (3) / Sensors (1)

Sensor Setup

AI#:# (Type)

Span= #### Zero=####

OK? $ (Y/N)

While the left and right arrows are flashing, press
PREV or NEXT to scroll through all of the analog
inputs and RTDs that can be set up. Press UP/DOWN

to modify the sensor type when it is flashing. Input
the span (the sensor value that corresponds to a
20mA signal), then input the Zero (the sensor value
that corresponds to a 4mA signal). Table 12 shows

the default values for each analog input or RTD.

Table 13 shows all of the possible analog input or
RTD types.

Sensor

Default Default Default Field Field Field

Number

Type

Span Zero Type Span Zero

AI #1

Suc Press

100

0

AI #2

Sys Press

300

0

AI #3

None

0

0

AI #4

None

0

0

RTD #1 Suc Temp

N/A

N/A

RTD #2 Sys Temp

N/A

N/A

Table 12: Sensor Setup Variables

Analog Input Types

RTD Types

None

None

Suc Press

Suc Temp

Sys Press

Sys Temp

Flow

Sup Temp

Temp

Ret Temp

Press

Diff Temp

Table 13: Possible Sensor Types

Note: Only one sensor of each type can be set up. If

a type is chosen that is already used for another sen-

sor or RTD channel, the other sensor or RTD input
will be given a type of “None”.

4.2

Pump Setup Menu

Path: Status Screens / Setup (3) / Pumps (2)

Pump Menu: # 0=Exit

1=Number of Pumps

2=Nameplate Data

3=Reset Pmp Runtime

4.2.1

Number of Pumps

Path: Status Screens / Setup (3) / Pumps (2) / Number
of Pumps(1)

Total # Pumps: #

# Jockey Pumps: #

# Standby Pumps: #

OK? $ (Y/N)

See Table 14 for a description of the variables.

Variable Description

Default Range Field

Value

Value

Total # The total number of

3

1-6

Pumps pumps in the system.

#

Jockey pumps will always

0

0-5

Jockey be first in the staging
Pumps sequence. Alternation will

not change this designation.

Jockey Pumps will be

assigned to the lowest

pump numbers starting

with Pump # 1.

#

A standby pump will only

0

0-5

Standby operate if a duty pump
Pumps fails. The last pumps in the

staging sequence will be

designated as the standby

pumps.

Table 14: Number of Pumps Variables

4.2.2

Pump Nameplate Data

Path: Status Screens / Setup (3) / Pumps (2) /
Nameplate Data (2)

Pump# 1 Data

HP : ###.#

Amps: ###.#

GPM : ####

OK? $

Press PREV or NEXT to scroll though all of the

pumps. See Table 15 for a description of the vari-

ables.

Section 4 — Setup Menu