Technologic
®
Constant Speed Pump Controller Installation, Operation and Maintenance Manual
15
From the status screens, shown in section 3.4, press
the SETUP key to get to the Setup Menu shown
below. Field values columns are provided to record
user setup information for future reference. For the
remainder of this manual, the path to navigate to a
particular screen will be given as follows: Path: Status
Screens/Setup(3).
Setup Menu: # 0=Exit
1=Sensors 4=Test
2=Pumps 5=Alrm/Evt
3=System 6=EZ-Start
4.1
Sensor Setup
Path: Status Screens / Setup (3) / Sensors (1)
←
Sensor Setup →
AI#:# (Type)
Span= #### Zero=####
OK? $ (Y/N)
While the left and right arrows are flashing, press
PREV or NEXT to scroll through all of the analog
inputs and RTDs that can be set up. Press UP/DOWN
to modify the sensor type when it is flashing. Input
the span (the sensor value that corresponds to a
20mA signal), then input the Zero (the sensor value
that corresponds to a 4mA signal). Table 12 shows
the default values for each analog input or RTD.
Table 13 shows all of the possible analog input or
RTD types.
Sensor
Default Default Default Field Field Field
Number
Type
Span Zero Type Span Zero
AI #1
Suc Press
100
0
AI #2
Sys Press
300
0
AI #3
None
0
0
AI #4
None
0
0
RTD #1 Suc Temp
N/A
N/A
RTD #2 Sys Temp
N/A
N/A
Table 12: Sensor Setup Variables
Analog Input Types
RTD Types
None
None
Suc Press
Suc Temp
Sys Press
Sys Temp
Flow
Sup Temp
Temp
Ret Temp
Press
Diff Temp
Table 13: Possible Sensor Types
Note: Only one sensor of each type can be set up. If
a type is chosen that is already used for another sen-
sor or RTD channel, the other sensor or RTD input
will be given a type of “None”.
4.2
Pump Setup Menu
Path: Status Screens / Setup (3) / Pumps (2)
Pump Menu: # 0=Exit
1=Number of Pumps
2=Nameplate Data
3=Reset Pmp Runtime
4.2.1
Number of Pumps
Path: Status Screens / Setup (3) / Pumps (2) / Number
of Pumps(1)
Total # Pumps: #
# Jockey Pumps: #
# Standby Pumps: #
OK? $ (Y/N)
See Table 14 for a description of the variables.
Variable Description
Default Range Field
Value
Value
Total # The total number of
3
1-6
Pumps pumps in the system.
#
Jockey pumps will always
0
0-5
Jockey be first in the staging
Pumps sequence. Alternation will
not change this designation.
Jockey Pumps will be
assigned to the lowest
pump numbers starting
with Pump # 1.
#
A standby pump will only
0
0-5
Standby operate if a duty pump
Pumps fails. The last pumps in the
staging sequence will be
designated as the standby
pumps.
Table 14: Number of Pumps Variables
4.2.2
Pump Nameplate Data
Path: Status Screens / Setup (3) / Pumps (2) /
Nameplate Data (2)
←
Pump# 1 Data →
HP : ###.#
Amps: ###.#
GPM : ####
OK? $
Press PREV or NEXT to scroll though all of the
pumps. See Table 15 for a description of the vari-
ables.
Section 4 — Setup Menu