Setup menu – Bell & Gossett S14367B Technologic Constant Speed Pump Controller User Manual
Page 18
![background image](/manuals/311132/18/background.png)
Technologic
®
Constant Speed Pump Controller Installation, Operation and Maintenance Manual
18
Setup Menu
The pump staging sequence, which is shown in sec-
tion 3.4.4, may be alternated automatically or manu-
ally. To manually alternate the sequence, press ALT
from the status screens, then press “Y” and ENTER
at the prompt. Automatic and manual alternation
methods use the Basis and Dur variables shown
below. See Table 19 for a description of the
Alternation variables.
Variable Units Description
Default Range Field
Value
Value
Alt
N/A Automatic Alter-
None None,
nation Method
Timed,
None: disables
Daily,
automatic alternation
Weekly,
Timed: alternates
Monthly
based on the “Period”
Daily: alternates daily
based on the “Time”
Weekly: alternates
weekly based on the
“Time” and the “Day”
Monthly: alternates
monthly based on the
“Time” and the “Day”
Basis
N/A Seq: the next pump in
Seq
Seq,
the sequence will
Pmp
become the lead pump
Tm
after alternation
Pmp Tm: the pump
with the lowest run time
will become the lead
pump after alternation
Dur
Sec- Amount of time that
10
0-99
onds the running pumps will
remain on during
alternation
Time
N/A Time, in 24hr format,
0:00
0:00-
at which the pumps will
23:59
be alternated for daily,
weekly, or monthly
alternation
Day
N/A Day of the week (1=
1
1-28
Monday…7=Sunday)
or month (day of month)
on which the pumps
will be alternated
Period Hours Time between pump
168
0-999
alternations when using
“Timed” alternation
Table 19: Alternation Variables
4.3.3
Pump Exercise
Path: Status Screens / Setup (3) / System (3) /
Exercise (3)
Pump Exercise
Period : ###Hr
Duration : ###Sec
OK? $
Pump exercising will ensure that no pumps go for
long periods of time without running. Note that
automatic alternation can also provide this function-
ality. Pump exercising will only occur when the sys-
tem is started and in automatic operation. All pumps
which need exercising will exercise on startup. All
exercising events will be logged in the Exercise Log
shown in section 4.7.5.5. See Table 20 for a descrip-
tion of the Exercise variables.
Variable Units Description
Default Range Field
Value
Value
Period Hours Amount of time between
0
0-999
automatic exercising of
the pumps, a value of 0
disables pump exercising
Dur-
Sec- Amount of time pumps
0
0-999
ation
onds will be exercised, all
pumps which have not
run in the last period
will be exercised
simultaneously
Table 20: Pump Exercise Variables
4.3.4
Start/Stop
Path: Status Screens / Setup (3) / System (3) / Start /
Stop (4)
Start/Stop
Method: $$$$$$$$$
OK? $
The controller can be started or stopped in a variety
of ways. This method will always be displayed next
to the start/stop/ready status in the Tech Status screen
shown in section 3.4.1. See Table 21 for a description
of the Start/Stop Methods.
Variable Description
Default Range Field
Value
Value
Method Keypad: Use the keypad to
Keypad Keypad,
start and stop the system
Remote,
Remote: Use “Start/Stop
Serial,
Sw” tied to DI #7
Sched-
Serial: Use “System Start/
uled
Stop” shown in appendix C
Scheduled: Use scheduling
to start and stop the system,
see section 4.3.5
Table 21: Start/Stop Variables