beautypg.com

Setup menu – Bell & Gossett S14367B Technologic Constant Speed Pump Controller User Manual

Page 17

background image

Technologic

®

Constant Speed Pump Controller Installation, Operation and Maintenance Manual

17

Setup Menu

The staging method chosen will be displayed in the

upper left corner. Press PREV or NEXT to scroll
through each staging occurrence. The staging num-

bers will increment to indicate which occurrence is
being shown. Set the value and the proof time for

each staging occurrence.

4.3.1.2 Secondary Staging

Path: Status Screens / Setup (3) / System (3) / Staging

(1) / Secondary Staging (2)

Sec Stg Mthd: Method

Stg :###(U) PT: ##s

Dstg:###(U) PT: ##s

Dynamic Stg:$ OK? $

See Table 17 for a description of the Secondary

Staging variables

Variable Units Description

Default Range Field

Value

Value

Sec Stg N/A Secondary staging

Pressure Power,

Methd

method. This will be

Amps,

used if the sensor for

Press,

the primary method

D Temp,

fails. Power, Amps

Flow,

and flow staging

Temp

require nameplate

data to be set up.

See section 4.2.2.

Stg

(U) The value at which

System 0-999

pumps will stage on.

Pressure

The units depend on the – 10

staging type. This is the

stage 1-2 value and will

be used for each staging

occurrence unless Dy-

namic Stg is set to “Y”.

Dstg

(U) The value at which

System 0-999

pumps will stage off.

Pressure

The units depend on the – 3

staging type. This is the

destage 2-1 value and

will be used for each

destaging occurrence

unless Dynamic Stg is

set to “Y”.

PT

Sec- The proof timer that

5

5-99

onds will elapse before

staging pumps on/off.

Dynamic N/A Select “Y” for Dynamic “N”

Y/N

Stg

Stg to choose different

staging and destaging

values for each staging

occurrence. A separate

screen will be displayed

to allow for these inputs.

Table 17: Secondary Staging Variables

If “Y” was selected for Dynamic Stg, the screen

shown below will be displayed.

Method Value Time

Stg1-2: ###(U) ##s

Dst2-1: ###(U) ##s

OK? $ (Y/N)

The staging method chosen will be displayed in the

upper left corner. Press PREV or NEXT to scroll
through each staging occurrence. The staging num-

bers will increment to indicate which occurrence is
being shown. Set the value and the proof time for

each staging and destaging occurrence.

4.3.1.3 Force Destage/Minimum Pump Run Time

Path: Status Screens / Setup (3) / System (3) / Staging

(1) / Force Dstg / Min Run (3)

Force Dstg/Min Run

Force Dstg Tmr=##Min

Min Run Timer =##Min

OK? $ (Y/N)

See Table 18 for a description of the Force Destage/

Minimum Pump Run Time variables.

Variable Units Description

Default Range Field

Value

Value

Force Min- Maximum time a lag

60

0-99

Dstg

utes pump will run prior

Tmr

to destaging auto-

matically, a value of 0

disables forced

destaging. See section

3.4.5 for display of

timer status.

Min Min- Minimum time a lag

5

0-99

Run

utes pump must run prior

Timer

to destaging, a value

of 0 effectively dis-

ables the minimum

run timer. See section

3.4.5 for display of

timer status.

Table 18: Force Destage/Minimum Pump Run Time Variables

4.3.2

Alternation

Path: Status Screens / Setup (3) / System (3) /
Alternation (2)

Alt Method: $$$$$

Basis:$$$$$ Dur:##s

Time:##:## Day: ##

Period:###Hrs OK? $