Technologic

®

Constant Speed Pump Controller Installation, Operation and Maintenance Manual

37

Description

Read

Write Range/Value

Modbus

Bacnet

Lonworks

N2

Address

Address NV Index Address

System Start/Stop Status

X

1=Start, 0=Stop

10001

BI 1

0

BI 1

System Auto/Manual Status

X

1=Auto, 0=Manual

10002

BI 2

1

BI 2

General Alarm

X

1=Fail, 0=OK

10003

BI 3

2

BI 3

Reset Required

X

1=Reset is Required, 0=OK

10004

BI 4

3

BI 4

AI 1 Fail

X

1=Fail, 0=OK

10005

BI 5

4

BI 5

AI 2 Fail

X

1=Fail, 0=OK

10006

BI 6

5

BI 6

AI 3 Fail

X

1=Fail, 0=OK

10007

BI 7

6

BI 7

AI 4 Fail

X

1=Fail, 0=OK

10008

BI 8

7

BI 8

RTD 1 Fail

X

1=Fail, 0=OK

10009

BI 9

8

BI 9

RTD 2 Fail

X

1=Fail, 0=OK

10010

BI 10

9

BI 10

Battery Fail

X

1=Fail, 0=OK

10011

BI 11

10

BI 11

Low Suction Pr (AI)

X

1=Fail, 0=OK

10012

BI 12

11

BI 12

Low Suction Pr (Switch)

X

1=Fail, 0=OK

10013

BI 13

12

BI 13

High Suction Pr

X

1=Fail, 0=OK

10014

BI 14

13

BI 14

Low System Pr

X

1=Fail, 0=OK

10015

BI 15

14

BI 15

High System Pr

X

1=Fail, 0=OK

10016

BI 16

15

BI 16

NFSD (Diff. Temp)

X

1=Fail, 0=OK

10017

BI 17

16

BI 17

NFSD (Flow Switch)

X

1=Fail, 0=OK

10018

BI 18

17

BI 18

Low Level

X

1=Fail, 0=OK

10019

BI 19

18

BI 19

High System Temperature

X

1=Fail, 0=OK

10020

BI 20

19

BI 20

Pump1 DP Fail

X

1=Fail, 0=OK

10021

BI 21

20

BI 21

Pump2 DP Fail

X

1=Fail, 0=OK

10022

BI 22

21

BI 22

Pump3 DP Fail

X

1=Fail, 0=OK

10023

BI 23

22

BI 23

Pump4 DP Fail

X

1=Fail, 0=OK

10024

BI 24

23

BI 24

Pump5 DP Fail

X

1=Fail, 0=OK

10025

BI 25

24

BI 25

Pump6 DP Fail

X

1=Fail, 0=OK

10026

BI 26

25

BI 26

Pump1 OL Fail

X

1=Fail, 0=OK

10027

BI 27

26

BI 27

Pump2 OL Fail

X

1=Fail, 0=OK

10028

BI 28

27

BI 28

Pump3 OL Fail

X

1=Fail, 0=OK

10029

BI 29

28

BI 29

Pump4 OL Fail

X

1=Fail, 0=OK

10030

BI 30

29

BI 30

Pump5 OL Fail

X

1=Fail, 0=OK

10031

BI 31

30

BI 31

Pump6 OL Fail

X

1=Fail, 0=OK

10032

BI 32

31

BI 32

CAN fail

X

1=Fail, 0=OK

10033

BI 33

32

BI 33

Voltage Tolerance Fail

X

1=Fail, 0=OK

10034

BI 34

33

BI 34

Voltage Fail

X

1=Fail, 0=OK

10035

BI 35

34

BI 35

System Start/Stop

X

1=Start, 0=Stop

00001

BO 1

60

BO 1

System Reset

X

Positive Edge = Reset/Silence

00002

BO 2

61

BO 2

Pump Alternation

X

Positive Edge = Alternate

00003

BO 3

62

BO 3

Pump1 State

X

0=Disabled, 1=Run, 2=Ready, 30001

AI 1

44

ADI 1

3=Failed

Section C — Serial Communications Points