Technologic

®

Constant Speed Pump Controller Installation, Operation and Maintenance Manual

23

Setup Menu

4.4.5

Key Test

Path: Status Screens / Setup (3) / Test (4) / Key (5)

Key Test

Press a key to test

Press clear to exit

Press any key except for the CLEAR key, and the dis-

play will confirm that the key is working by display-
ing the key name. Press CLEAR to exit.

4.4.6

Display Test

Path: Status Screens / Setup (3) / Test (4) / Disp (6)

The display will show all black characters. Press

CLEAR to exit.

4.4.7

Comm Test

Path: Status Screens / Setup (3) / Test (4) / Comm (7)

Comm Test

ITT Read: ####

ITT Write: ####

Press Clear to Exit

If the controller is communicating properly with the
building automation system, both numbers will con-

tinue increasing in value. For Modbus protocol, the

read and write numbers should be equal and increas-
ing with every poll. For BACnet, both numbers
should be increasing, but they will not be equal. The

write value will increase even when not connected.
For the Metasys N2 protocol, both numbers should

be increasing but may not be equal. This test feature
is not supported for Lonworks. If both numbers are

not increasing in value, the controller is not commu-
nicating properly. Check the wiring at the terminal

blocks. See section 4.3.10 for more information on
communications setup. Press CLEAR to exit this test.

4.5

Alarms/Events Menu

Path: Status Screens / Setup (3) / Alrm/Evt (5)

Alarm Menu: # 0=Exit

1=Pump Failure

2=Low System

3=High System

Alarm Menu: # 0=Exit

4=Low Suction

5=High Suction

6=NFSD

Alarm Menu: # 0=Exit

7=High Temp

8=Low Level

9=Volts Tolerance

Press UP/DOWN to view the entire menu.

4.5.1

Pump Failure

Path: Status Screens / Setup (3) / Alrm/Evt (5) /

Pump Failure (1)

Pump Failure

DP Switch Pr Tm: ##s

OK? $ (Y/N)

See Table 30 for a description of the Pump Failure
variables.

Variable Units Description

Default Range Field

Value

Value

DP

Sec- Proof timer prior to

10

0-99

Switch onds setting a pump fail

Pr Tm

alarm after receiving

a continuous high sig-

nal from a DP switch

Table 30: Pump Failure Variables

4.5.2

Low System Pressure

Path: Status Screens / Setup (3) / Alrm/Evt (5) /
Low System (2)

Low Sys Press: ##PSI

Low Sys Pr Tm: ##s

Alarm:$ Stop Pumps:$

OK? $ (Y/N)

See Table 31 for a description of the Low System
Pressure variables.