Setup menu – Bell & Gossett S14367B Technologic Constant Speed Pump Controller User Manual
Page 23

Technologic
®
Constant Speed Pump Controller Installation, Operation and Maintenance Manual
23
Setup Menu
4.4.5
Key Test
Path: Status Screens / Setup (3) / Test (4) / Key (5)
Key Test
Press a key to test
Press clear to exit
Press any key except for the CLEAR key, and the dis-
play will confirm that the key is working by display-
ing the key name. Press CLEAR to exit.
4.4.6
Display Test
Path: Status Screens / Setup (3) / Test (4) / Disp (6)
The display will show all black characters. Press
CLEAR to exit.
4.4.7
Comm Test
Path: Status Screens / Setup (3) / Test (4) / Comm (7)
Comm Test
ITT Read: ####
ITT Write: ####
Press Clear to Exit
If the controller is communicating properly with the
building automation system, both numbers will con-
tinue increasing in value. For Modbus protocol, the
read and write numbers should be equal and increas-
ing with every poll. For BACnet, both numbers
should be increasing, but they will not be equal. The
write value will increase even when not connected.
For the Metasys N2 protocol, both numbers should
be increasing but may not be equal. This test feature
is not supported for Lonworks. If both numbers are
not increasing in value, the controller is not commu-
nicating properly. Check the wiring at the terminal
blocks. See section 4.3.10 for more information on
communications setup. Press CLEAR to exit this test.
4.5
Alarms/Events Menu
Path: Status Screens / Setup (3) / Alrm/Evt (5)
Alarm Menu: # 0=Exit
1=Pump Failure
↑
2=Low System
↓
3=High System
Alarm Menu: # 0=Exit
4=Low Suction
↑
5=High Suction
↓
6=NFSD
Alarm Menu: # 0=Exit
7=High Temp
↑
8=Low Level
↓
9=Volts Tolerance
Press UP/DOWN to view the entire menu.
4.5.1
Pump Failure
Path: Status Screens / Setup (3) / Alrm/Evt (5) /
Pump Failure (1)
Pump Failure
DP Switch Pr Tm: ##s
OK? $ (Y/N)
See Table 30 for a description of the Pump Failure
variables.
Variable Units Description
Default Range Field
Value
Value
DP
Sec- Proof timer prior to
10
0-99
Switch onds setting a pump fail
Pr Tm
alarm after receiving
a continuous high sig-
nal from a DP switch
Table 30: Pump Failure Variables
4.5.2
Low System Pressure
Path: Status Screens / Setup (3) / Alrm/Evt (5) /
Low System (2)
Low Sys Press: ##PSI
Low Sys Pr Tm: ##s
Alarm:$ Stop Pumps:$
OK? $ (Y/N)
See Table 31 for a description of the Low System
Pressure variables.