Installing the module, 2 module configuration and assembly – GE Industrial Solutions DC OEM Module For use with Gerapid DC Circuit Breaker User Manual
Page 11

DC OEM MODULE FOR USE WITH GERAPID CIRCUIT BREAKERS
Chapter 4 Installing the Module
2011-04-26 S47183Ee rev.01
Design and specifications are subject to change without notice
11
Installing the Module
4-1 General Notes
This chapter contains instructions for installing the GE DC OEM
Module.
CAUTION: Personnel installing this equipment must be 
thoroughly familiar with this instruction manual and all articles 
of the National Electrical Code applicable to the installation of 
this equipment. In addition, all drawings, both mechanical 
installation and electrical, must be understood and strictly 
followed to prevent damage to the module. 
Environmental Requirements
The module as provided is designed for indoor installations only 
and should be placed in an indoor area where clean, dry air is free 
to circulate around and above it. Since air is taken into the 
equipment at the bottom of each section and exhausted at the 
top, a location with good airflow must be provided for efficient 
operation. 
A minimum of 30 inches of clear space above the equipment is 
recommended. In order to properly withdraw the trolley there 
should be at least 7 foot of space in the front of the module. 
 
NOTE: See Appendix C for sketches concerning layout.
Foundation Requirements
The foundation requirements detailed in this chapter should be 
strictly adhered to. 
Fig.41-1 Module anchor bolt hole locations
The foundation must be strong enough to prevent sagging due to
the weight of the completed switchgear structure and to 
withstand the impact loading caused by the opening of the 
breakers under fault conditions. The impact loading is 
approximately 1-1/2 times the static load.
The foundation must be flat and level in all planes with maximum 
deviation of 0.8 inch at the length of 3 foot. The module should be 
anchored to the floor through holes shown on Fig. 41-1 using 
7/16” or metric M12 grade 5 steel bolts.
4-2 Module Configuration and Assembly
Multiple Modules Side by Side Assembly
Modules can be connected together to form switchgear lineups. 
To bolt two modules together, edge trim strips must be removed. 
Special connection spacers must be used and are inserted into 12 
hex shaped cut outs visible in the sidewalls. Fig. 42-1 shows the 
location of the front 4 connection spacer openings. Location of all 
openings and installation tips are shown in Appendix G.
A Module Coupling Kit can be ordered under Cat. No.: 289169. 
Each kit consists of 12 Connection spacers, bolts and washers 
necessary to connect two adjacent modules. 
NOTE: See Appendix D for connection drawings.
Fig. 42-1 Location of front module connection spacers
Module Preparation
Every module is suitable for operating either with manually or 
motor operated trolley. Depending on the type of trolley being 
utilized, a locking plate in the module may need to be removed: 
 
 
If motor operated trolley is going to be used with the 
Module, remove the locking plate. 
If manually operated trolley is going to be used with the 
module, keep the locking plate in place  
 
See Fig. 41-1 and Fig. 42-2 to locate locking plate. 
NOTE: Look for the yellow warning label placed on the 
module’s floor to find bottom guide rail and the plate. 
Connection Spacers
12 per side-by-side.
Top View on the floor.
Anchor Points 
 
Use M12 or 
7/16” grade 5
bolts.
Locking Plate
