Identity object, class 0x01, Services, Class attributes – GE Industrial Solutions AF-300 P11_G11 Ethernet Interface User Manual
Page 45: Instance attributes

Appendix C – Ethernet/IP Objects
39
Identity Object, Class 0x01
Services
Class services
Get Attribute All
Get Attribute Single
Instance services
Get Attribute All
Get Attribute Single
Reset
Class Attributes
# Access
Name
Type
Value Description
1 Get Revision
UINT
0x0001 Revision
1
Instance Attributes
# Access
Name
Type
Value Description
1
Get
Vendor ID
UINT
0x005A
HMS Industrial Networks AB
2
Get
Device type
UINT
0x000C
Communication Adapter
3
Get
Product code
UINT
0x012C
OPC-G11S-ETN drive adapter
Struct of:
-
Version X.YY
USINT XX
Major product version of this
communication module.
4 Get Revision
USINT YY
Minor product version of this
communication module
5 Get Status
WORD -
Status of the device, see table
below.
6 Get Serial
number
UDINT Serial
number
This is the serial number of the
product, assigned when the module
is produced.
7 Get Product
name
SHORT_S
TRING
“OPC-
G11S-
ETN”
The module’s product name.
Status Attribute
Extended Device Status (Bit 4-7)
Bit 0
Owned, shall be set when at least one
connection
is
configured.
Bit 1
Reserved, set to 0.
Bit 2
Configured, is always set to 1.
Bit 3
Reserved, set to 0.
Bit 4-7
See extended device status
Bit 8
Is set for minor recoverable faults.
Bit 9
Is set for minor recoverable faults.
Bit 10
Is set for major recoverable faults.
Bit 11
Is set for major unrecoverable faults.
Bit 12-15 Reserved, set to 0.
0000 = Unknown
0010 = Faulted I/O connection
0011 = No I/O connection established
0100 = Non volatile configuration bad
0110 = Connection in run mode