Bus configuration parameters, Operation configuration parameters – GE Industrial Solutions AF-300 P11_G11 Ethernet Interface User Manual
Page 18

Installation and Configuration
12
Bus Configuration Parameters
Some basic settings can be accessed via the keypad. For instructions how to use the keypad, see the drive’s
user manual.
Drive
parameter
Name Description
o30 Communication
rate
0 = Auto negotiate
1 = 100 Mbps, Full duplex
2 = 100 Mbps, half duplex
3 = 10 Mbps, Full duplex
4 = 10 Mbps, half duplex
o31 Disable
FTP 0 = Enable FTP server
1 = Disable FTP server
o32 Reserved
-
o33 IDLE
action 0 = If the EtherNet/IP header indicates idle, an error is sent to
the drive
1 = The run/idle bit is ignored
o34 Modbus/TCP
timeout
Sets the maximum time between Modbus/TCP commands
before a time-out is detected.
The value is multiplied with 100 ms to give the timeout from
100ms-25.5s.
Operation Configuration Parameters
These parameters configure the link option control and set the drive’s reaction upon a network loss event.
Drive
parameter
Name Description
H30 Link
function 0 = Command and freq. from drive
1 = Command from drive, freq. from option card
2 = Command from option card, freq. from drive
3 = Command and freq. from option card
o27
Loss of network
behaviour
0 = Immediate trip (ERR5)
1 = Trip after timer setting, o28
2 = Re-check after timer setting o28
3 = Ignore communication error
o28
ERR5 timer setting
(used with o27)
ERR5 timer setting, 0.0 – 60s