Appendix A - EGD, EtherNet/IP IO Format
26
Data Produced by the Drive
Produced data is located in assembly instance 100 on EtherNet/IP and Consumed Exchange 1(C1) on EGD.
Position Description
Word 0 (16 Bit)
Operation status monitor 1
Word 1 (16 Bit)
Operation status monitor 2
Word 2 (16 Bit)
Output frequency monitor
Operation Status Monitor 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
- -
WR
RL
ALM
DEC
ACC
IL
VL
TL
NUV
BRK
INT
EXT
REV
FWD
FWD
1: In forward command
REV
1: In reverse command
EXT
1: In DC breaking or in preparatory excitation
INT 1:
No
output
BRK 1:
In
breaking
NUV
1: DC link voltage is establishment
(Under voltage condition at 0)
TL
1: In torque limiting
VL
1: In voltage limiting
IL
1: In current limiting
ACC 1:
In
acceleration
DEC 1:
In
deceleration
ALM 1:
Alarm
RL
1: Remote (Run command or Frequency command is valid from link)
WR
1: Fieldbus writing right, 0: Keypad writing right
Operation Status Monitor 2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
- - - - - - - - - - - -
SWM2
RDY
FDT
FAR
FAR
1: Frequency (speed) arrival
FDT
1: Frequency (speed) detection
RDY
1: Ready for operation
SWM2
1: Motor 2 switching