Data format [14]: operation command, Data format [15]: universal output terminal – GE Industrial Solutions AF-300 P11_G11 Ethernet Interface User Manual
Page 41

Appendix B - Drive Parameters
35
Data Format [12]: Index Data (ACC/DEC Time, Display Coefficient)
(MSB)
(LSB)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Polarity
0 0 0
Index
portion
Data
portion
Field Description
Polarity
0: Positive
(+)
1: Negative
(-)
Index portion
0: 0.01 *
001–999
(0.00 – 9.99)
1: 0.1 *
100–999
(10.0 – 99.9)
2: 1
*
100–999
(100 – 999)
3: 10
*
100–999
(1000 – 9990)
Data portion
Value
Example) F07 (Acceleration time 1) = 20.0 s,
20.0 = 0.1 * 200 = 0400
H
+ 00C8
H
= 04C8
H
Data Format [14]: Operation Command
(MSB)
(LSB)
15 14
13 12
11 10 9 8 7 6 5 4 3 2 1 0
RST 0 0 0 0 X9 X8 X7 X6 X5 X4 X3 X2 X1 REV
FWD
(All bits are ON or active by 1)
Field Description
RST Alarm
X9-X1
Multi function command
REV
Reverse rotation command
FWD
Forward rotation command
Example) If M13 (Operation command, Final command) = FWD, X1, X5 = ON
0000 0000 0100 0101b = 0045H
Data Format [15]: Universal Output Terminal
(MSB)
(LSB)
15 14 13 12
11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0 0 0 0 Y5
Y4
Y3
Y2
Y1
Y5-Y1 = Universal command (All bits are ON by 1)
Example) If M15 (Universal output terminal) = Y1, Y5 = ON,
0000 0000 0001 0001
b
.= 0011
H