GE Industrial Solutions Galaxy Pulsar Edge User Manual
Page 183

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011
183
Factory Default
Factory 24V
Rectifier Default
Factory 48V
Rectifier
Default
Category
Description
Range
Factory
Factory 24V
Factory 48V
obj,attr
Daylight Saving End
mon:wk:dow:min
mon:-1:dom:min
"11:1:0:120"
PS1,DSE
Time zone offset
-840 - +840
minutes (±14
hours)
0
PS1,TZO
Uninstall Equipment Timeout
0 to 60s
15
PS1,UET
Critical Equals Major
1=Enabled
0=Disabled
1
PS1,CEM
User Password
"lineage"
PAS U,
Super-user Password
"super-user"
PAS S,
Administrator Password
"administrator"
PAS A,
Low Voltage Disconnects
Battery Disconnect 1
Battery Disconnect Control Mode
0=none,
1=voltage
2=voltage/time,
3=adaptive
1
CN1,DAM
Battery Disconnect Time Delay
0:0:0 to 4:59:59
0:00:00
CN1,DDY
Battery Reconnect Control Mode
0=none,
1=voltage
2=voltage/time
1
CN1,RAM
Battery Reconnect Time Delay
0 to 300 sec
0
CN1,RDY
Battery Disconnect Description
<=32 Chars
"LVBD"
CN1,DES
Battery Disconnect Open
Description
<=32 Chars
"LVBD Open"
CNO1,DES
Battery Disconnect Open Front
Panel Description
<=32 Chars
"LVBD Open"
CNO1,FDS
Battery Disconnect Failed
Description
<=32 Chars
"LVBD Failed"
CNF1,DES
Battery Disconnect Failed Front
Panel Description
<=32 Chars
"LVBD Failed"
CNF1,FDS
Load Disconnect 1
Load 1 Disconnect
1=Enabled
0=Disabled
0
CN2,ENA
Load 1 Disconnect Control Mode
0=none,
1=voltage
2=voltage/time
1
CN2,DAM
Load 1 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.50
43.00
CN2,DTH
Load 1 Disconnect Time Delay
0:0:0 to 4:59:59
0:00:00
CN2,DDY
Load 1 Reconnect Control Mode
0=none,
1=voltage
2=voltage/time
1
CN2,RAM
Load 1 Reconnect Voltage
19.5 to 27
-39.0 to -55.0V
22.00
44.00
CN2,RTH
Load 1 Reconnect Time Delay
0 to 300 sec
0
CN2,RDY
Load 1 Disconnect Description
<=32 Chars
"LVLD1"
CN2,DES
Load 1 Disconnect Open
Description
<=32 Chars
"LVLD1 Open"
CNO2,DES
Load 1 Disconnect Open Front Panel
Description
<=32 Chars
"LVLD1 Open"
CNO2,FDS
Load 1 Disconnect Failed
Description
<=32 Chars
"LVLD1 Failed"
CNF2,DES
Load 1 Disconnect Failed Front
Panel Description
<=32 Chars
"LVLD1 Failed"
CNF2,FDS
Load Disconnect 2
LV Load 2 Disconnect
1=Enabled
0=Disabled
0
CN3,ENA
LV Load 2 Disconnect Control
Mode
0=none,
1=voltage
2=voltage/time
1
CN3,DAM
LV Load 2 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.00
42.00
CN3,DTH
LV Load 2 Disconnect Time Delay
0:0:0 to 4:59:59
0:00:00
CN3,DDY
LV Load 2 Reconnect Control Mode
0=none,
1=voltage
2=voltage/time
1
CN3,RAM