Lighting Controller Modbus Register Map
Compact Event Log
40
Compact Event Log
The Lighting Controller uses an object known as the
compact event log to store system events. This is a first-in,
first-out rotary buffer with a depth adjustable to a
maximum of 1500 events. Each event has eight
components that can be reported. If the buffer overflows,
the oldest event is discarded to make room for the latest. A
register is available that contains the number of events in
the log. If the log is empty and an attempt is made to read
out an event, an exception is returned. Events are read
using Function Code 04.
Event Definitions
Table 80 lists the types of events that can be present in the
compact event log. Asking for more events than are
present in the event log causes an exception. Read register
20001 and 20002 to get the number of events and ask for
12n registers to get the n
th
number of entries.
Offset Modbus reg. DB size
Property
Format
Range
Type
0
20001- 20002 Byte
Total Events
Int
1 – 1500
R
Alarm Output Ref.
2
20003
Word
Device No
Word
0 - 65535
R
3
20004
Word
Object Type
Word
0 – 65535
R
4
20005
Word
Object Instance
Word
0 – 65535
BO= 4
BV= 5
R
5
20006
Byte
Alarm Ack
Int
0/1
R
6
20007- 20008 Byte
Alarm Values
Int
0 - 65535,
0 - 65535
R
Array of
1500
Event Entries
8
20009
Hrs/Mins
Int
0 – 23 | 0 - 59
R
9
20010
Seconds/Hundredths of sec
Int
0 – 59 | 0 - 99
R
10
20011
Week of Day / Day
Int
0 – 07 | 0 – 31
R
11
20012
Month / Year
Int
0 – 12 | 0 – 99
R
12
20013
Event Type
Int
Enum
R
13
20014
Event Argument
Int
Enum
R
Event Object Ref.
14
20015
Object Type
WORD
0 – 65535
R
15
20016
Object Instance
WORD
0 – 65535
R
16 –
12007
20017 –
32008
1499 more Event entries
(8 registers per entry)
12007 registers per CEL
Table 79. Registers comprising the compact event log.
Each event record is a block of eight registers starting
from 20009. Note that these registers are read only. The
Alarm Output Ref and Alarm Ack properties are editable.
Note that if Alarm Output Reference does not exist, all
three registers are filled with 0xFFFF.
Compact Event Log Registers
The registers of the compact event log are listed in Table
79.