A series, Sample packets – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual
Page 35

A Series
®
Lighting Controller Modbus Register Map
Lighting Group Objects
29
Sample Packets
The following are examples of requests to specific setup
registers.
Read for LG1 OutOfService Value
Table 49 is an example of read for LG1 OutOfService,
Value and Current Priority for Reg4001–Reg4003
(Function 3, LG 1in map).
Request
Response
Field Name
Hex Field Name
Hex
Device Address
01
Device Address
01
Function
03
Function
03
Register Address Hi
0F
Byte Count
06
Register Address Lo
A0
Register Value Hi (4001)
00
No. of Registers Hi
00
Register Value Lo (4001)
00
No. of Registers Lo
03
Register Value Hi (4002)
00
Packet CRC Hi
Register Value Lo (4002)
02
Packet CRC Lo
Register Value Hi (4003)
00
Register Value Lo (4003)
06
Packet CRC Hi
Packet CRC Lo
Table 49. Sample packets for read for Reg4001–Reg4003.
Response is as follows:
Reg4001 (OutOfService) 0x0000 – FALSE,
Reg4002 (Value) 0x0002 – Override
Reg4003 (Current Priority) 0x0006 – Priority 6
Read LG Photocell Reference
Table 50 is an example of read LG Photocell Reference
(Object Type, Object Instance and Panel Number) for
Reg. 4009–Reg4011 (Function 3, LG1 in map).
The response is Photocell Reference Object Type 1
(AI), Object Instance 2, Panel Number 100.
Request
Response
Field Name
Hex Field Name
Hex
Device Address
01
Device Address
01
Function
03
Function
03
Register Address Hi
0F
Byte Count
06
Register Address Lo
A8
Register Value Hi (4009)
00
No. of Registers Hi
00
Register Value Lo (4009)
64
No. of Registers Lo
03
Register Value Hi (4010)
00
Packet CRC Hi
Register Value Lo (4010)
00
Packet CRC Lo
Register Value Hi (4011)
00
Register Value Lo (4011)
02
Packet CRC Hi
Packet CRC Lo
Table 50. Sample packets for read LG photocell reference for Reg4009–4011.
Read Lighting Output Array
Table 51 is an example of read Lighting Output Array
Entry 2 Reg4035–Reg4042 (Function 3, LG1 in map).
Request
Response
Field Name
Hex Field Name
Hex
Device Address
01
Device Address
01
Function
03
Function
03
Register Address Hi
0F
Byte Count
10
Register Address Lo
C2
Register Value Hi (4035)
00
No. of Registers Hi
00
Register Value Lo (4035)
64
No. of Registers Lo
08
Register Value Hi (4036)
00
Packet CRC Hi
Register Value Lo (4036)
04
Packet CRC Lo
Register Value Hi (4037)
00
Register Value Lo (4037)
02
Register Value Hi (4038)
00
Register Value Lo (4038)
64
Register Value Hi (4039)
00
Register Value Lo (4039)
0D
Register Value Hi (4040)
00
Register Value Lo (4040)
66
Register Value Hi (4041)
00
Register Value Lo (4041)
00
Register Value Hi (4042)
00
Register Value Lo (4042)
02
Packet CRC Hi
Packet CRC Lo
Table 51. Sample packets for read for lighting output array.
The response to reading Array Index 2 of Lighting
Output, which consists of Output Reference and Switch
Reference, is as follows:
Reg4035–Reg3037 Output Reference object:
0x006400040002 - 100.BO2
Reg4038–Reg4040 Switch Reference object:
0x0063000E0065 - 100.MI101
Reg4041 Reference Value: 00000
Reg4042 Switch Value: 0002
Single Write OFF to Lighting Group 1
Table 52 is an example of a single write OFF (0x0000)
to LG1 Value Reg4002 (Function 6, LG 1in map). Note
that OutOfService is automatically set to TRUE with
this write.
Request
Response
Field Name
Hex Field Name
Hex
Device Address
01 Device Address
01
Function
06 Function
06
Register Address Hi
0B Register Address Hi
0B
Register Address Lo
B9 Register Address Lo
B9
Register Value Hi
00 Register Value Hi
00
Register Value Lo
00 Register Value Lo
00
Packet CRC Hi
Packet CRC Hi
Packet CRC Lo
Packet CRC Lo
Table 52. Sample packets for single write OFF to LG 1.