Environmental specifications, Car2912te series front-end, Preliminary data sheet – GE Industrial Solutions CAR2912TE series User Manual
Page 6: Emc compliance

GE
Preliminary Data Sheet
CAR2912TE series front-end
Input: 90Vac to 264Vac; Output: 12Vdc @ 2900W; 3.3 or 5Vdc @ 4A Standby
October 21, 2013
©2013 General Electric Company. All rights reserved.
Page 6
Environmental Specifications
Parameter
Min
Typ
Max
Units
Notes
Ambient Temperature
-10
70
°C
Derated above 50°C
Storage Temperature
-40
85
°C
Operating Altitude
2250/7382
m/ft
Non-operating Altitude
8200/30k
m / ft
Power Derating with Temperature
2.5
%/°C
50°C to 70°C
Power Derating with Altitude
2.0
°C/301 m
°C/1000 ft
Above 1524 m/5000 ft
Acoustic noise
55
45
dbA
Full load
Half load
Over Temperature Protection
125/110
°C
Shutdown / restart
Humidity
Operating
Storage
30
10
95
95
%
Relative humidity, non-condensing
Shock and Vibration acceleration
2.4
Grms
Meet IPC-9592B Class II
EMC Compliance
Parameter
Criteria
Standard
Level
Test
AC input
Conducted emissions
EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2
A*
0.15 – 30MHz
0 – 2 KHz
Radiated emissions**
EN55022
A*
30 – 10000MHz
AC input
immunity
Voltage dips
EN61000-4-11
B
-30%, 10ms
B
-60%, 100ms
B
-100%, 5sec
Voltage surge
EN61000-4-5
A
4kV, 1.2/50µs, common mode
A
2kV, 1.2/50µs, differential mode
Fast transients
EN61000-4-4
B
5/50ns, 2kV (common mode)
Enclosure
immunity
Conducted RF fields
EN61000-4-6
A
130dBµV, 0.15-80MHz, 80% AM
Radiated RF fields
EN61000-4-3
A
10V/m, 80-1000MHz, 80% AM
ENV 50140
A
ESD
EN61000-4-2
B
4kV contact, 8kV air
*
Note: Contact the factory for a recommended external EMI filter to meet Class B emissions
**
Radiated emissions compliance is contingent upon the final system configuration.
6
Designed to start at an ambient down to -40°C; meet spec after ≅ 30 min warm up period, may not meet operational limits below -10°C.