Input: 90Vac to 264Vac; Output: 12Vdc @ 2900W; 3.3 or 5Vdc @ 4A Standby
October 21, 2013
©2013 General Electric Company. All rights reserved.
Page 3
12V
dc
MAIN OUTPUT (continued)
Parameter
Symbol
Min
Typ
Max
Unit
Ripple and noise
-120
120
mV
P-P
Turn-ON overshoot
+3
%
Turn-ON delay
T
2
sec
ON/OFF delay time
40
ms
Turn-ON rise time (10 – 90% of V
out
)
50
ms
Transient response 50% step [10%-60%, 50% - 100%]
(dI/dt – 1A/µs, recovery 300µs)
V
O
-5
+5
%V
O
Programmable range (hardware & software)
10.8
13.2
V
DC
Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)
13.8
14.8
15.8
V
DC
Output current 180 ≥ V
IN
≥ 264
90 ≥ V
IN
≥ 132
I
O
0
242
117
A
DC
Current limit, Hiccup (programmable level)
110
130
% of FL
Active current share
-5
+5
% of FL
STANDBY OUTPUT
Parameter
Symbol
Min
Typ
Max
Unit
Set point
V
O
3.3 / 5.0
V
DC
Overall regulation (load, temperature, aging)
V
O
-5
+5
%
Ripple and noise
50
mV
P-P
Output current
I
O
0
4
A
DC
Overload protection -
110
150
% of FL
Isolation Output/Frame
100
V
DC
General Specifications
Parameter
Min
Typ
Max
Units
Notes
Reliability, 25°C
50°C
320,000
100,000
Hrs
Full load, ; MTBF per SR232 Reliability protection for
electronic equipment, method I, case III,
Service Life
10
Yrs
Full load, excluding fans
Weight
Feature Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. See
Control and Status for additional information.
Parameter
Symbol
Min
Typ
Max
Unit
ON/OFF (Needs to be pulled HI via an external resistor)
Logic High (Module ON)
I
IH
20
µA
V
IH
0.7V
DD
12
V
DC
Logic Low (Module OFF)
I
IL
4
mA
V
IL
0
0.8
V
DC
3
Measured across a 10µf tantalum and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth