3.6.13 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and
over-current protected according to national/international regulations.
Short-circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. GE recommends using the fuses mentioned below to protect
service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case of a short-circuit
on the motor output.
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. Fuses or circuit breakers can be used to provide the over-
current protection in the installation. Over-current protection must always be carried out according to national regulations.
380-500 V, frame sizes 4X, 5X and 6X
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V, or 600V depending on the drive voltage
rating. With the proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
AF-650
GP
Bussmann
E1958
JFHR2**
Bussmann
E4273
T/JDDZ**
SIBA
E180276
RKI/JDDZ
LittelFuse
E71611
JFHR2**
Ferraz-
Shawmut
E60314
JFHR2**
Bussmann
E4274
H/JDDZ**
Bussmann
E125085
JFHR2*
Internal
Option
Bussmann
125 HP
FWH-
300
JJS-
300
2028220-
315
L50S-300
A50-P300
NOS-
300
170M3017
170M3018
150 HP
FWH-
350
JJS-
350
2028220-
315
L50S-350
A50-P350
NOS-
350
170M3018
170M3018
200 HP
FWH-
400
JJS-
400
206xx32-
400
L50S-400
A50-P400
NOS-
400
170M4012
170M4016
250 HP
FWH-
500
JJS-
500
206xx32-
500
L50S-500
A50-P500
NOS-
500
170M4014
170M4016
300 HP
FWH-
600
JJS-
600
206xx32-
600
L50S-600
A50-P600
NOS-
600
170M4016
170M4016
Table 3.4: For Unit Sizes 41, 42, 43, and 44,380-500 V
AF-650 GP
Bussmann PN*
Rating
Ferraz
Siba
350 HP
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
400 HP
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
500 HP
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
550 HP
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
Table 3.5: For Unit Sizes 51 and 52, 380-500 V
AF-650 GP
Bussmann PN*
Rating
Siba
Internal Bussmann Option
600 HP
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
650 HP
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
750 HP
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
900 HP
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
1000 HP
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
1200 HP
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
Table 3.6: Unit Sizes 61, 62, 63, and 64, 380-500 V
AF-650 GP
Bussmann PN*
Rating
Siba
600 HP
170M8611
1100 A, 1000 V
20 781 32.1000
650 HP
170M8611
1100 A, 1000 V
20 781 32.1000
750 HP
170M6467
1400 A, 700 V
20 681 32.1400
900 HP
170M6467
1400 A, 700 V
20 681 32.1400
1000 HP
170M8611
1100 A, 1000 V
20 781 32.1000
1200 HP
170M6467
1400 A, 700 V
20 681 32.1400
Table 3.7: Unit Sizes 61, 62, 63, and 64, Inverter module DC Link Fuses, 380-500 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be
substituted for external use
**Any minimum 500 V UL listed fuse with associated current rating may be used to meet UL requirements.
AF-650 GP High Power Operating Instructions
58