Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual
Page 113

Mains Supply 3 x 525- 690 VAC
AF-650 GP
150 HP
200 HP
250 HP
300 HP
Heavy Duty/Light Duty*
HD
LD
HD
LD
HD
LD
HD
LD
Typical Shaft output at 550 V
[kW]
90
110
110
132
132
160
160
200
Typical Shaft output at 575 V
[HP]
125
150
150
200
200
250
250
300
Typical Shaft output at 690 V
[kW]
110
132
132
160
160
200
200
250
IP21/Nema 1 Drive Type
41
41
42
42
IP54/Nema 12 Drive Type
41
41
42
42
IP00 Open Chassis Drive
Type
43
43
44
44
Output current
Continuous
(at 550 V) [A]
137
162
162
201
201
253
253
303
Intermittent (60 sec over-
load)
(at 550 V) [A]
206
178
243
221
302
278
380
333
Continuous
(at 575/ 690 V) [A]
131
155
155
192
192
242
242
290
Intermittent (60 sec over-
load)
(at 575/ 690 V) [A]
197
171
233
211
288
266
363
319
Continuous KVA
(at 550 V) [KVA]
131
154
154
191
191
241
241
289
Continuous KVA
(at 575 V) [KVA]
130
154
154
191
191
241
241
289
Continuous KVA
(at 690 V) [KVA]
157
185
185
229
229
289
289
347
Max. input current
Continuous
(at 550 V ) [A]
130
158
158
198
198
245
245
299
Continuous
(at 575 V) [A]
124
151
151
189
189
234
234
286
Continuous
(at 690 V) [A]
128
155
155
197
197
240
240
296
Max. cable size, mains mo-
tor, load share and brake
[mm
2
(AWG)]
2 x 70 (2 x 2/0)
2 x 70 (2 x 2/0)
2 x 185 (2 x 350 mcm) 2 x 185 (2 x 350 mcm)
Max. external pre-fuses [A]
1
315
350
350
400
Estimated power loss
at rated max. load [W]
4)
2664
3114
2953
3612
3451
4292
4275
5156
Weight,
Unit Size IP21, IP 54 [kg]
96
104
125
136
Weight,
Unit Size IP00 [kg]
82
91
112
123
Efficiency
4)
0.98
Output frequency
0 - 600 Hz
Heatsink
overtemp.
trip
85 °C
90 °C
110 °C
110 °C
Power card ambient trip
60 °C
* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s
AF-650 GP High Power Operating Instructions
112
5