Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual
Page 114
Mains Supply 3 x 525- 690 VAC
AF-650 GP
350 HP
400 HP
500 HP
Heavy Duty/Light Duty*
HD
LD
HD
LD
HD
LD
Typical Shaft output at 550 V [kW]
200
250
250
315
315
355
Typical Shaft output at 575 V [HP]
300
350
350
400
400
450
Typical Shaft output at 690 V [kW]
250
315
315
400
355
450
IP21/Nema 1 Drive Type
42
42
51
IP54/Nema 12 Drive Type
42
42
51
IP00 Open Chassis Drive Type
44
44
52
Output current
Continuous
(at 550 V) [A]
303
360
360
418
395
470
Intermittent (60 sec overload)
(at 550 V) [A]
455
396
540
460
593
517
Continuous
(at 575/ 690 V) [A]
290
344
344
400
380
450
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
435
378
516
440
570
495
Continuous KVA
(at 550 V) [KVA]
289
343
343
398
376
448
Continuous KVA
(at 575 V) [KVA]
289
343
343
398
378
448
Continuous KVA
(at 690 V) [KVA]
347
411
411
478
454
538
Max. input current
Continuous
(at 550 V ) [A]
299
355
355
408
381
453
Continuous
(at 575 V) [A]
286
339
339
390
366
434
Continuous
(at 690 V) [A]
296
352
352
400
366
434
Max. cable size, mains, motor and
load share [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
4 x 240
(4 x 500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses [A]
1
500
550
700
Estimated power loss
at rated max. load [W]
4)
4875
5821
5185
6149
5383
6449
Weight,
Unit Size IP21, IP 54 [kg]
151
165
263
Weight,
Unit Size IP00 [kg]
138
151
221
Efficiency
4)
0.98
Output
frequency
0 - 600 Hz
0 - 500 Hz
0 - 500 Hz
Heatsink overtemp. trip
110 °C
110 °C
85 °C
Power card ambient trip
60 °C
60 °C
68 °C
* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s