Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual
Page 116

Mains Supply 3 x 525- 690 VAC
AF-650 GP
900 HP
1000 HP
1200 HP
1250 HP
1350 HP
Heavy Duty/Light Duty*
HD
LD
HD
LD
HD
LD
HD
LD
HD
LD
Typical Shaft output at
550 V [kW]
500
560
560
670
670
750
750
850
850
1000
Typical Shaft output at
575 V [HP]
650
750
750
950
950
1050
1050
1150
1150
1350
Typical Shaft output at
690 V [kW]
630
710
710
800
800
900
900
1000
1000
1200
IP21/Nema 1 and IP54/
Nema 12 Drive Types
without/with options
cabinet
61/ 63
61/ 63
61/ 63
62/ 64
62/ 64
Output current
Continuous
(at 550 V) [A]
659
763
763
889
889
988
988
1108
1108
1317
Intermittent (60 sec
overload)
(at 550 V) [A]
989
839
1145
978
1334
1087
1482
1219
1662
1449
Continuous
(at 575/ 690 V) [A]
630
730
730
850
850
945
945
1060
1060
1260
Intermittent (60 sec
overload)
(at 575/ 690 V) [A]
945
803
1095
935
1275
1040
1418
1166
1590
1386
Continuous KVA
(at 550 V) [KVA]
628
727
727
847
847
941
941
1056
1056
1255
Continuous KVA
(at 575 V) [KVA]
627
727
727
847
847
941
941
1056
1056
1255
Continuous KVA
(at 690 V) [KVA]
753
872
872
1016
1016
1129
1129
1267
1267
1506
Max. input current
Continuous
(at 550 V ) [A]
642
743
743
866
866
962
962
1079
1079
1282
Continuous
(at 575 V) [A]
613
711
711
828
828
920
920
1032
1032
1227
Continuous
(at 690 V) [A]
613
711
711
828
828
920
920
1032
1032
1227
Max. cable size, motor
[mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size,mains
[mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size, load-
sharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake
[mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-fuses
[A]
1
1600
2000
Estimated power loss
at rated max. load [W]
4)
Weight,
Unit Size IP21, IP 54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight, Rectifier Module
[kg]
102
102
102
136
136
Weight, Inverter Module
[kg]
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink overtemp. trip
85 °C
Power card ambient trip
68 °C
* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s
1) For type of fuse see section Fuses.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the frequency converter
and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
Keypad and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses. (Though typical
only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
AF-650 GP High Power Operating Instructions
115
5