beautypg.com

Digital inputs, Analog inputs, Analog outputs – B&B Electronics ZXT9-IOA-KIT - Manual User Manual

Page 44: Modbus frequency / counters inputs

background image

Configuration & Operation

38

Manual Documentation Number: ZXTx-IO-x-4113m

6.1.3.2.2 Digital Inputs

There are 2 digital inputs available in the I/O modules and their addressing is as follows:

Digital Outputs

Modbus Memory

Address

Digital Input 1

10001

Digital Input 2

10002

Fig 6-9 Digital Input Memory Table

When a digital input is ON, the I/O module sets the corresponding Modbus register as a ‘1’. Otherwise, the register value is ‘0’.

As an example, when the Digital Input (DO1) on the Xtreme Module goes ON, the Modbus register memory location 00002 will
be set to a value of 1.

6.1.3.2.3 Analog Inputs

There are two 16-bit analog inputs available in the I/O modules and their addressing is as follows:

Analog Inputs

Modbus Memory

Address

Analog Input 1

30001

Analog Input 2

30002

Fig 6-10 Analog Input Memory Table

The I/O module sets the register value based on the analog signal level.

As an example, for a 0-10V selection, when the analog input 1 is 5V, the memory location 30001 will read 32,768

Refer to Appendix F for analog data scaling.

6.1.3.2.4 Analog Outputs

There are two 16-bit analog inputs available in the I/O modules and their addressing is as follows:

Analog Outputs

Modbus Memory

Address

Analog Output1

40001

Analog Output 2

40002

Fig 6-11 Analog Output Memory Table

To set a 5 mA output current at analog output terminal 2, when a selection of 0- 20mA is made, the Modbus Master must set a
value of 16,384 in the memory location 40002.

Refer to Appendix F for analog data scaling.

6.1.3.2.5 Modbus Frequency / Counters Inputs

In Modbus mode, a Zlinx Xtreme I/O supports the two Digital Inputs in the following modes:

 Frequency
 Counters (Accumulators)