Power & i/o terminals, Usb port, Peer-to-peer slave mode – B&B Electronics ZXT9-IOA-KIT - Manual User Manual
Page 17: Modbus mode, 7 power & i/o terminals, 8 usb port
Product Introduction
Manual Documentation Number: ZXTx-IO-x-4113m
11
The following default settings established when the mode is changed:
ZXT24-IO-222R2
ZXT9-IO-222R2
Peer-to-Peer master mode
Radio Network:
0x0c
0x00
Radio ID Number:
0x11
0x11
Radio Output Power:
(4) 63mw
(4) 1w
Number of Retries:
10
10
AES Security:
Disabled
Disabled
P2P Address:
1
1
OTA Baud:
Fixed*
115200
P2P Polling Rate:
0 sec
0 sec
Peer-to-Peer slave mode
Radio Network:
0x0c
0x00
Radio ID Number:
0x11
0x11
Radio Output Power:
(4) 63mw
(4) 1w
Number of Retries:
10
10
AES Security:
Disabled
Disabled
P2P Address:
1
1
OTA Baud:
Fixed*
115200
P2P Slave Timeout:
30 sec
30 sec
Modbus mode
Radio Network:
0x0c
0x00
Radio ID Number:
0x11
0x11
Radio Output Power:
(4) 63mw
(4) 1w
Number of Retries:
10
10
AES Security:
Disabled
Disabled
Modbus Address:
1
1
OTA Baud:
Fixed*
115200
Modbus Slave Timeout:
30 sec
30 sec
* -
“Fixed” for OTA Baud means that this parameter can’t be changed and is equal to 250 Kbps.
Refer to section 6 for parameter descriptions.
2.5.7 Power & I/O Terminals
Screw terminals are provided for Power & I/O interface connections as shown. Refer to Chapter 4 for wiring information.
2.5.8 USB Port
The USB port is used to configure the I/O module and for firmware updates. The I/O module must be connected and powered for the
Zlinx Manager Software to detect the IO module. Refer to section 4 for software installation and section 5 for programming the unit.